When it comes to fire safety within a building, fire extinguishers are not typically the first protection method that comes to mind. Fire sprinklers, fire alarm systems, smoke detectors – all are much more commonly considered when evaluating the fire safety of a building or space. However, portable fire extinguishers do play a role in the overall protection strategy of a building and are still required by the International Building Code (IBC) and International Fire Code (IFC) in most buildings. This post will explore the specific requirements, installation guidelines, and considerations for architects, designers, and building safety professionals. All code references in this post are to the 2021 IBC and IFC or the 2022 Edition of NFPA 10, the Standard for Portable Fire Extinguishers. What is a Portable Fire Extinguisher According to NFPA 10, a portable fire extinguisher is “A portable device, carried or on wheels and operated by hand, containing an extinguishing agent that can be expelled under pressure for the purpose of suppressing or extinguishing fire.” Classifying Fire Hazards and Selecting the Right ExtinguisherFire extinguishers are categorized based on the type of fire hazard they are designed to address. Let's break down the classifications of fire hazard types:
In addition to the fire hazard classification, the IBC and IFC also consider the severity of the fire hazard, including light/low hazard, ordinary/moderate hazard and extra/high hazard. The required type of fire extinguisher is based on the classification of the fire hazard while the required size of fire extinguishers is primarily based on the severity of the hazard. We’ll cover this in more detail later in this post. Where Are Fire Extinguishers Required Portable fire extinguishers must be installed in multiple locations depending on the type of occupancy and the specific hazards present in a building. These requirements are found in IBC 906.1: 1. General Occupancies Fire extinguishers are required in Group A, B, E, F, H, I, M, R-1, R-2, R-4, and S occupancies, which encompass a wide variety of buildings:
Exceptions to the Occupancy Requirements:
2. Cooking Equipment: Fire extinguishers are required within 30 feet of commercial cooking equipment. Additionally, in Group I-1, I-2 Condition 1 and R-2 college dormitories, fire extinguishers are required within 30 feet of domestic cooking equipment. 3. Flammable or Combustible Liquids: Fire extinguishers are required where flammable or combustible liquids are stored, used or dispensed. 4. During Construction: Fire extinguishers are required on every floor of structures under construction with the exception of Group R-3 occupancies. See IFC 3315.1 for additional information. 5. Other Locations: Fire extinguishers are required in certain special situations by the IFC. Refer to IBC Table 906.1 which provides a list of these situations. 6. Special Hazard Areas: Fire extinguishers are required in special hazard areas including laboratories, computer rooms and generator rooms where required by the fire code official. Extinguisher Size, Distribution, and Rating The IBC requires fire extinguishers to be sized and distributed based on a variety of factors including fire classification, hazard type, and floor area. Class A Fire HazardsFire extinguishers for Class A fire hazards must comply with the following per IBC 906.3.1:
Class B Fire HazardsFire extinguishers in locations with flammable or combustible liquids with depths less than or equal to ¼-inch must comply with the following per IBC 906.3.2:
Fire extinguishers in locations with flammable or combustible liquids with depths greater than ¼-inch must comply with the requirements found in NFPA 10. Class C Fire Hazards Fire extinguishers for Class C fire hazards must be selected and placed based on the anticipated Class A or B hazard. Class D Fire Hazards Fire extinguishers in locations with combustible metals must comply with requirements found in NFPA 10. Cooking Equipment Fires Fire extinguishers in locations with cooking equipment must be approved and compatible with the automatic fire extinguishing system used for the cooking equipment. If the cooking equipment involves solid fuels, vegetable/animal oils or fats, a Class K fire extinguishers is required. Refer to Section 906 of the IFC for additional information. Installation Requirements and Guidelines Correct installation is as crucial as the right selection of fire extinguishers. Section [F] 906.9 outlines specific requirements for installation: 1. Installation Height
2. Floor Clearance
3. Conspicuous and Unobstructed Location
4. Cabinet Requirements
Conclusion Portable fire extinguishers are required in most buildings and occupancies. Selection and placement of portable fire extinguishers varies based on the type of hazards present and and the type of extinguisher being provided.
Need assistance on your specific project? Add Campbell Code Consulting to your team. They are a full-service code consulting and fire protection engineering firm that can help you navigate complex code challenges.
2 Comments
James Lucking
4/29/2025 11:10:13 am
This article would be more informative if it included a citation for the code and section where low, moderate and high fire hazard is found.
Reply
Dwight Havens
5/14/2025 05:04:44 pm
Article did a good job at outlining the code and standard requirements referenced.
Reply
Leave a Reply. |
Categories
All
Sign up to receive Building Code Blog Updates |