The Building Code Blog
  • Home
  • Blog
  • About
  • PE Roadmap
  • Tools
    • Allowable Height & Area Calculator - Separated Mixed Occupancy
    • Allowable Height & Area Calculator - Non-Separated Mixed Occupancy
    • Average Grade Plane Calaculator
    • Calculated Fire Resistance for Wood Walls
    • Fire and Smoke Damper Tool
    • Fire Wall/Exterior Wall Intersection Tool
    • Frontage Calculator
    • IBC Occupant Load Calculator
    • Plumbing Fixture Calculator
    • Stair Pressurization Estimator
  • Startup

The Building Code Blog

Mitigating Dead End Corridors

4/15/2020

16 Comments

 
​For years, architect clients have asked me for solutions to mitigate a dead end corridor condition. As a quick reference, dead ends are limited to 20 feet, except in Groups B, E, F, I-1, M, R-1, R-2, R-4, S and U with a full NFPA 13 sprinkler system, where the limit is increased to 50 feet (2015 IBC 1020.4).
Picture
Up until recently, my normal suggestion has been to place a cross-corridor door to break up the length of any one corridor segment to less than 50 (or 20) feet. This has been accepted in numerous jurisdictions and also validated by an ICC staff opinion that I requested on the topic. In many cases, I have seen the cross corridor door on magnetic hold opens, to release upon activation of the fire alarm system
Cross corridor door on magnetic hold opens
Cross-corridor door on magnetic hold opens.
But on a recent project, a local AHJ has taken the stance that a cross corridor door does not mitigate a dead end condition. I scheduled a meeting with the AHJ to explain how this has been done on other projects and to share the ICC interpretation, but they were reluctant to budge. After some negotiations, the AHJ allowed the door, but insisted that it not be held open and also required a large "Not an Exit" sign on the door itself.

I have drawn up a similar situation in the image below. The corridor is serving a Group A occupancy, so the dead end limit is 20 feet. The added door is shown in red.
Dead End Sketch
Sketch showing the dead end condition with added cross-corridor doors.

Dead End Corridors: What Do You Think?

Do cross-corridor doors mitigate the 20 foot dead end limit? Do you think they should be permitted to be held open?
Let me know your thoughts in the comment box!
16 Comments
Matt Benfer
4/16/2020 09:45:54 am

Sounds like a valid approach. I think the "Not an Exit" sign is a must have on this type of a door as the whole purpose is to prevent the rest of the normally dead end corridor as being attempted to be used for egress. Whether the door is held open or not doesn't seem to be a huge issue to me, except that I would think that a door which is not magnetically held open is probably more likely to be propped open by other means, this negating the door.

Reply
Chris Campbell
4/16/2020 09:58:50 am

Thanks for the reply, Matt. I like the point about the door being more likely to be propped open if the magnetic hold opens are not provided...will have to bring that up next time I chat with this particular AHJ!

Reply
Brian Lukus
4/16/2020 06:14:46 pm

I have seen this situation approved with a locking hardware set on the cross-corridor door in addition to the door holder and signage. Some other things to consider:

1) How many times can you add cross corridor doors? Twice? three times? If this were a B occupancy, are you proposing a door can be added to get another 50ft of dead end?
2) The intent of the dead end length is to limit the path of travel such that the occupant(s) have to turnaround to find an exit. If the door is on a hold open, the fire could be elsewhere in the building, (doors only required to release on the smoke next to the door per NFPA 72), so what is the held open door preventing in a fire emergency that has not spilled out into the corridor? The emergent building evacuation is still occurring and the occupant(s) could be mentally stressed from the fire incident and miss the exit.
3) I know Codes are written around fire emergencies, however they are also accepted for other emergent building evacuation. This held open cross corridor door does nothing to prevent the dead end condition in non-fire emergencies. Yes not a fire Code mandate to design for non-fire emergencies but as life safety professionals, is it prudent design to think about this topic especially in assembly occupancies where these other emergencies have occurred?

Reply
Chris Campbell
4/17/2020 07:57:56 am

Hi Brian,

Thanks so much for sharing your thoughts!

1) I think the common path of travel limit prevents the cross-corridor door from being applied multiple times. For a Group B, this is typically 100 feet, so you would likely only be able to provide one cross-corridor door and still meet the 100 foot common path.

2) Good point. I do appreciate the previous comment above that if the door is not held open by the fire alarm system, it is more likely to be propped open with the door stop.

3) I think this is a fair point to consider. Fire is just one type of emergency - there are clearly many others. I would note that in a non-fire emergency, you would not have a smoke-filled corridor, so the chance of missing the exit in the first place is much less.

Reply
Kelly Kidwell
5/9/2020 11:49:44 am

2) You can require all doors on magnetic holds to close upon alarm regardless of alarm initiation point. It's all in the wiring and programming, but that could mitigate concerns regarding doors being held open when no smoke is in that corridor.

Bruce Verhei
4/16/2020 09:57:25 pm

Good evening.

Exit distances were extended in almost every use or occupancy except H shortly before creation of the I-code series. The IBC exiting chapter most closely followed the legacy UBC. Scissor stairs, less restrictive second way out of boiler rooms, and some other minor items came from the other two codes. More or less Chapter 10 of the UBC was cut and pasted in creation of the new code.

That Chapter 10 was result of recent complete rewrite. The consultant Boeing hired to do the rewrite and seek successful adoption of this replacement was able to convince many of the obvious: We use travel distance in part as a surrogate for exiting time. By exiting time we almost always are considering needed time to leave before smoke, meaning sight obscuring, toxic, maybe hot, and choking gases are thick enough to impede travel to persons not wearing SCBA.

A door across a dead end does nothing to substitute for travel time to point of having a choice of more smoky or less smoky pathway. If concept is that you are providing a location to shelter in place considerably more would be needed.

Requiring rating, and having every door from a space opening into the exit access to be smoke rated and be self-closing with mag-hold open might be an acceptable alternative where not all ready required.

Pressurization of the exit pathways is the gold standard.

I do not see adding a door as mitigating the original problem.

I would favor a code change that extended dead end distance where sprinklers and pressurization are provided.

Best.

Bruce Verhei
Olympia, WA

Reply
Chris Campbell
4/17/2020 07:59:13 am

Thanks for sharing your thoughts Bruce!

Reply
Ryan Indorf
4/27/2020 11:54:07 pm

If an AHJ is hesitant to approve a cross-corridor door to prevent continued travel in the opposite direction of an exit, I would be curious to hear their thoughts on interruption gates within exit stairs.

In regards to an automatic closing door in this scenario, I agree with the above comment that all emergency egress events should be considered and not solely fire. However, it may also be worth considering what might happen over time if the door is NOT held open. A wedge in the door completely defeats the purpose of the door, regardless of the emergency.

Reply
Kelly Kidwell
5/9/2020 11:57:09 am

I think in a lot of ways, dead ends are bad design. Bad for egress and life safety, but also bad for circulation under normal circumstances. My first line of defense is trying to get the architects to improve their design and eliminate long dead ends altogether. Normally a long dead end is an opportunity for another through-way for circulation or an opportunity to add some closets.

In my mind, a case where you need several doors to eliminate a dead end is unacceptable. There needs to be a rethinking of the space--or why not an additional exit? At that point you're probably about to hit the limit for travel distance anyway.

A door is the last resort when nothing else can work. And to me it seems less risky in a fully sprinklered building.

Reply
Chris Campbell
5/18/2020 11:30:05 am

Thanks for the thoughts Kelly, hope all is well with you!

Reply
David Dillon link
10/18/2021 07:31:25 am

Hello,

Great article, I find myself dealing with my first dead-end issue here at work in NC. The corridor is a connection between 2 town owned buildings to prevent people having to go outside. The 2 building are a community center and a senior center. The corridor is 30' long and sprinklered, a set of doors on one side that the owner wants to lock to prevent after hours entry into the senior center.

I would like to email the drawing to the author for comment.

Reply
Chris Campbell
10/19/2021 08:53:39 am

Hi David,

Thanks for the comment. Please feel free to email me at Chris (at) buildingcode (dot) blog.

Regards,

Chris

Reply
James Samuelson link
2/1/2022 01:35:46 pm

"This has been accepted in numerous jurisdictions and also validated by an ICC staff opinion that I requested on the topic."

Can you share the ICC Staff opinion, I am running thru the same discussion here in Ohio.
Thanks!

Reply
Steve Bergeron
4/7/2022 02:03:51 pm

Is the consensus here that a cross-corridor wall and door would be treated like any other corridor wall/ door from a fire-rating standpoint?

For example, in a 3-story R2 apartment building, corridor walls are permitted to be 1/2 hr and doors are 20 min. Would there be any reason for the cross-corridor wall/door to be a higher rating?

Reply
Chris Campbell
4/7/2022 03:33:42 pm

I'm not aware of anything that would require a higher rating.

Reply
restorerz link
1/19/2023 08:59:35 am

Fire safety is important in order to: Reduce the risk of injury to employees and customers. Reduce damage to facility/building. Protect against possible fines.

Reply



Leave a Reply.

    Picture
    Interested in Sponsoring?

    Categories

    All
    Calculators
    Chapter 10 - Means Of Egress
    Chapter 11 - Accessibility
    Chapter 14 - Exterior Walls
    Chapter 1 - Scope And Administration
    Chapter 24 - Glass And Glazing
    Chapter 2 - Definitions
    Chapter 33 - Safeguards During Construction
    Chapter 4 - Special Detailed Requirements
    Chapter 5 - General Building Heights And Areas
    Chapter 6 - Types Of Construction
    Chapter 7 - Fire And Smoke Protection Features
    Chapter 9 - Fire Protection Systems
    Cheat Sheets

    RSS Feed

      Signup to Receive Building Code Blog Updates

    Submit

    Archives

    March 2023
    February 2023
    January 2023
    November 2022
    October 2022
    March 2022
    February 2022
    January 2022
    November 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019

Home

About

Blog

Contact

Copyright © 2019-2023 The Building Code Blog
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, including the author's employer and the International Code Council, nor does the presented material assume responsibility for its use.  Local codes and amendments may vary from the code requirements described herein. Fire protection and life safety systems constitute a critical component of public health, safety and welfare and you should consult with a licensed professional for proper design and code compliance.
  • Home
  • Blog
  • About
  • PE Roadmap
  • Tools
    • Allowable Height & Area Calculator - Separated Mixed Occupancy
    • Allowable Height & Area Calculator - Non-Separated Mixed Occupancy
    • Average Grade Plane Calaculator
    • Calculated Fire Resistance for Wood Walls
    • Fire and Smoke Damper Tool
    • Fire Wall/Exterior Wall Intersection Tool
    • Frontage Calculator
    • IBC Occupant Load Calculator
    • Plumbing Fixture Calculator
    • Stair Pressurization Estimator
  • Startup