The Building Code Blog
  • Home
  • Blog
  • About
  • PE Roadmap
  • Tools
    • Allowable Height & Area Calculator - Separated Mixed Occupancy
    • Allowable Height & Area Calculator - Non-Separated Mixed Occupancy
    • Average Grade Plane Calaculator
    • Calculated Fire Resistance for Wood Walls
    • Fire and Smoke Damper Tool
    • Fire Wall/Exterior Wall Intersection Tool
    • Frontage Calculator
    • IBC Occupant Load Calculator
    • Plumbing Fixture Calculator
    • Stair Pressurization Estimator
  • Startup

The Building Code Blog

Abutting Buildings: Three Code Approaches

12/30/2019

10 Comments

 
​If you are located in any major city, it’s likely that you can take a short walk down the street and find an instance of two adjacent buildings built up next to each other. If you’re out in the suburbs, you have probably seen this situation in the form of a row of townhouses. In the U.S., and other countries that adopt the International Building Code (IBC), these abutting buildings likely fall into one of the following cases:
  1. Two buildings located on separate lots, with both buildings abutting the property line that is between the two lots.
  2. Two buildings located on the same lot and abutting each other.

In either case, the IBC recognizes three distinct approaches for the wall(s) located between the abutting buildings. All references are to the 2015 IBC.

Walls Between Abutting Buildings

Picture
Abutting buidlings (image courtesty of agracier).
Abutting Exterior Walls
In both cases described above, the IBC allows for two abutting exterior walls to separate the two buildings. Since the two buildings have a zero fire separation distance, IBC 602 requires both walls to have a 1-hour fire-resistance rating for most occupancies (the requirement is higher for Groups M, F-1, S-1 and H). Similarly, IBC 705.8 prohibits openings in either of these walls.

Since both structures are considered separate and distinct buildings, structural independence is required. Both exterior walls are prohibited from bearing on each other, and the walls must be supported and braced by their respective buildings. This strategy is common when the two buildings have tenants or occupants who are unrelated to one another. Since openings between the buildings are not permitted, this approach is not practical when doors between buildings are required.

Once common exception is a concrete parking structure that is surrounded on all sides by a residential building. This type of project, often referred to as a “wrapper building” or “Texas Donut," utilizes a newly-added provision in the 2015 IBC 705.3, which allows protected openings between the buildings, as long as the opening in the parking garage building has a 1.5-hour fire resistance rating. The opening in the residential building does not require an opening protective in this case.
Pictured
A "Texas Donut" building under construction with the garage wall directly abutting the residential building wall (image courtesy of Payton Chung).
Fire Walls
Fire walls are required to be structurally independent from the building and must be continuous to the foundation. For two abutting buildings located on the same lot, this means that neither of the buildings can bear on the fire wall, which often results in the construction of three walls: the fire wall plus a separate exterior wall for each building. Floor assemblies can be connected to the fire wall using breakaway clips for continuity purposes, but they cannot be supported by the fire wall.

While the structural requirements for a fire wall are more restrictive than for exterior walls located near a lot line, fire walls are permitted to have protected openings. The openings in fire wall are limited to 156 SF, unless both buildings on either side of the fire wall are fully sprinkler-protected, in which case there is no limit to the area of openings (IBC 706.8). The required fire resistance rating of a fire wall is dependent on the occupancy classifications involved (IBC Table 706.4).
Picture
A fire wall creating two separate building (image courtesy of Ben Schumin).
Beginning in the 2015 IBC, code language was added to allow for compliance with NFPA 221 to satisfy the requirements of IBC 706. NFPA 221 contains provisions to allow double fire walls (two rated walls built next to each other) in lieu of one structurally independent fire wall. As shown in NFPA 221 Table 4.5 (copied below), two walls, each with a 2-hour fire resistance rating are deemed equivalent to a single 3-hour fire wall.
Fire Resistance Rating of Each Wall (hr)
Equivalent to Single Wall (hr)
3
4
2
3
1
2
This is similar to the abutting exterior wall strategy described previously, but the required wall rating is increased in order to meet the NFPA 221 requirements. Though this approach involves two separate walls, the entire assembly is considered a fire wall by the IBC. The fire wall strategy is best suited when there is a single owner or tenant in both buildings and openings between the two buildings are necessary.
Picture
Detail of a double fire wall (image courtesy of John Ivison).
Party Walls
The final option described in the IBC for the wall between two abutting buildings is a party wall. A party wall is described in the IBC as “Any wall located on a lot line between adjacent buildings, which is used or adapted for joint service between the two buildings…” (IBC 706.1.1).
​
This description indicates that party walls are specific to abutting buildings located on separate lots; a wall between buildings on the same lot would not be considered a party wall. Party walls must meet all of the requirements for fire walls, except that no openings are permitted. Generally, party walls require both owners to agree on how the wall will be used and any future design changes will be handled.

Conclusion

Abutting buildings can be found on the same lot or on two adjacent lots. Architects and engineers can choose between: (1) two abutting exterior walls, (2) a fire wall, or (3) a party wall when designing the wall between the two buildings. How have you approached designs in this situation? Comment and let us know!
10 Comments

Accessible Means of Egress Vs. Required Means of Egress

12/9/2019

4 Comments

 
When evaluating a building design for egress compliance, knowing the difference between the required and accessible means of egress is important. In this post, we’ll explore the difference between the required means of egress and the accessible means of egress and review the building design requirements for both. ​​
Picture

Means of Egress: Required vs. Accessible

All definitions and requirements are from the 2015 International Building Code (IBC). Note that the IBC does not always include the word “required” when referring to a means of egress. Generally, when the code references either “required means of egress” or “means of egress,” it’s referring to the first definition below. The IBC always uses the full term “accessible means of egress” when referring to the second definition.

Definitions (IBC 202):
Means of Egress: “A continuous and unobstructed path of vertical and horizontal egress travel from any occupied portion of a building or structure to a public way. A means of egress consists of three separate and distinct parts: the exit access, the exit and the exit discharge.”

Accessible Means of Egress: “A continuous and unobstructed way of egress travel from any accessible point in a building or facility to a public way.”

From these definitions, notice that both involve “a continuous and unobstructed…” path or way of egress, and that both will lead you “…to a public way.” But the definitions differ in starting point. For a means of egress, the starting point is “from any occupied portion of a building or structure,” whereas for an accessible means of egress, the starting point is “an accessible point in a building or facility.”

So simply from these definitions, we can gather an important distinction: an accessible means of egress only originates from an accessible point in a building or facility. If a building or portion of a building is not required to be accessible, it is not required to have an accessible means of egress (IBC 1009.1).

Means of Egress Components
A required means of egress consists of 3 distinct components: the exit access, the exit and the exit discharge.
Picture
Image courtesy of Access-Board.gov
Exit access is the first part of a means of egress and is the path between an occupied portion of the building and the exit. Typically, this consists of level walking surfaces such as corridors, and changes in level, such as exit access stairs and ramps. Any doorways along this path would be considered exit access doorways.

Next is the exit, which can be any of the following components: an exterior door at the level of exit discharge, interior exit stairways, interior exit ramps, exterior exit stairways, exterior exit ramps, exit passageways, and horizontal exits.

Finally, the exit discharge is the portion of a building or site between an exit and the public way. This could be both areas inside the building, such as a stairway that discharges through a lobby or vestibule, or outside the building, such as a courtyard located between an exterior exit door and the public way.
​
Accessible Means of Egress Components
​An accessible means of egress consists of one or more of the following components (IBC 1009.2):
Component​
IBC Reference
Accessible Routes
1104
Interior Exit Stairways
1009.3, 1023
Exit Access Stairways
1009.3, 1019.3, 1019.4
Exterior Exit Stairways
1009.3, 1027*
Elevators
1009.4
Platform Lifts
1009.5
Value
1026
Ramps
1012
Areas of Refuge
1009.6
Exterior Areas for Rescue Assistance
1009.7**
*serving levels other than the level of exit discharge
**serving exits at the level of exit discharge

You’ll notice that some of these components can also be part of a required means of egress – interior and exterior exit stairways, exit access stairways and ramps. But an accessible means of egress can include specific components for occupants who need accessible accommodations, such as elevators, lifts and exterior areas for rescue assistance, that are not part of the required means of egress.

Another important component is the accessible route, which is always required as part of an accessible means of egress. Since all portions of a building that are accessible require both an accessible route an accessible means of egress, you can’t provide one without the other. An accessible route could also be part of the required means of egress, but it’s not necessarily required.

Key Differences
Unlike the required means of egress, elevators can be used as a part of an accessible means of egress. And for buildings with an accessible floor located four or more stories above the level of exit discharge, at least one elevator is required as part of the accessible means of egress (IBC 1009.2.1).

Another important distinction exists for exit access stairs, which are permitted as part of the required means of egress and in certain cases as part of an accessible means of egress. However, exit access stairs that connect levels in the same story are not permitted as part of an accessible means of egress (IBC 1009.3). This means that stairs connecting levels within a single story, even if a just single step, are not considered part of an accessible means of egress.

Accessible Means of Egress: Where Required
The criteria for where an accessible means of egress is required are simple. Any accessible space within a building requires at least one accessible means of egress. Where two or more means of egress are required for any space, at least two accessible means of egress are required for that space (IBC 1009.1). There are several exceptions for existing buildings, mezzanines and assembly areas with seating areas served by aisles.
​
There is no code requirement for more than two accessible means of egress to serve any space.

Required Means of Egress: Where Required
The number of means of egress required from any space is governed by one of the following sections:

1006.2. If the number of occupants in a room or space or the common path of egress travel exceeds the value listed in Table 1006.2.1, two means of egress are required.

1006.3. Generally, all stories require at least two means of egress. If the story contains more than 500 occupants, the requirements increases to 3 means of egress, and increases again to a minimum of 4 when the story has an occupant load of more than 1,000.

The above code sections contain numerous exceptions, so be sure to review for your specific situation.

Conclusion

The IBC provides distinct criteria that defines both the means of egress and accessible means of egress, and where both are required. An accessible means of egress can include vertical transportation elements such as elevators and lifts that are not typically part of a required means of egress, and it will always include an accessible route from the area served.

All accessible portions in a building require at least one accessible means of egress, and where two or more means of egress are required, two accessible means of egress are required.
​
What questions to you have about accessible means of egress? Let us know in the comment section!
4 Comments

    Archives

    November 2022
    October 2022
    March 2022
    February 2022
    January 2022
    November 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019

    Categories

    All
    Calculators
    Chapter 10 - Means Of Egress
    Chapter 11 - Accessibility
    Chapter 14 - Exterior Walls
    Chapter 1 - Scope And Administration
    Chapter 24 - Glass And Glazing
    Chapter 2 - Definitions
    Chapter 33 - Safeguards During Construction
    Chapter 4 - Special Detailed Requirements
    Chapter 5 - General Building Heights And Areas
    Chapter 6 - Types Of Construction
    Chapter 7 - Fire And Smoke Protection Features
    Chapter 9 - Fire Protection Systems
    Cheat Sheets

    RSS Feed

      Signup to Receive Building Code Blog Updates

    Submit

Home

About

Blog

Contact

Copyright © 2019-2022 The Building Code Blog
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, including the author's employer and the International Code Council, nor does the presented material assume responsibility for its use.  Local codes and amendments may vary from the code requirements described herein. Fire protection and life safety systems constitute a critical component of public health, safety and welfare and you should consult with a licensed professional for proper design and code compliance.
  • Home
  • Blog
  • About
  • PE Roadmap
  • Tools
    • Allowable Height & Area Calculator - Separated Mixed Occupancy
    • Allowable Height & Area Calculator - Non-Separated Mixed Occupancy
    • Average Grade Plane Calaculator
    • Calculated Fire Resistance for Wood Walls
    • Fire and Smoke Damper Tool
    • Fire Wall/Exterior Wall Intersection Tool
    • Frontage Calculator
    • IBC Occupant Load Calculator
    • Plumbing Fixture Calculator
    • Stair Pressurization Estimator
  • Startup