The Building Code Blog
  • Home
  • Blog
  • About
  • PE Roadmap
  • Tools
    • Allowable Height & Area Calculator - Separated Mixed Occupancy
    • Allowable Height & Area Calculator - Non-Separated Mixed Occupancy
    • Average Grade Plane Calaculator
    • Calculated Fire Resistance for Wood Walls
    • Fire and Smoke Damper Tool
    • Fire Wall/Exterior Wall Intersection Tool
    • Frontage Calculator
    • IBC Occupant Load Calculator
    • Plumbing Fixture Calculator
    • Stair Pressurization Estimator
  • Startup

The Building Code Blog

2018 IBC Fire and Smoke Damper Cheatsheet

2/26/2021

6 Comments

 
After way too many hours of work, I'm excited to share this huge fire and smoke damper cheatsheet that goes through EVERY instance where the 2018 IBC requires a fire and smoke damper due to a wall/floor/ceiling penetration.
Picture

Download Now
6 Comments

Overview of Requirements for Open Stairs

2/18/2021

26 Comments

 
In the A/E design community, the term "open stair" is frequently used to describe a stair that is not enclosed with walls, partitions or barriers. While "open stair" is not a term used in the International Building Code, it generally aligns with a stairway (which is a defined term in the IBC) not used for egress purposes or an exit access stairway (also a defined term). The terms "communicating stair" and "convenience stair" are also used in the same line of discussion, though depending on the situation, these could be referring to communicating spaces or convenience openings, both types of vertical openings defined in NFPA 101.

In this post, we'll review the IBC requirements for open stairs and describe several code paths that can be used to provide open stairs in your design. I will use the term "open stair" throughout the post, but remember, since this is not a defined term, any formal documentation on drawings, plans etc. should use the proper nomenclature identified in this overview. This post will be limited to stairs within a building and will not address exterior stairways.

Open Stairs - 2018 IBC Code Paths

Stairway Connecting Levels within a Story
The first and most simple type of open stair connects one or more levels within a single story. This stair could be provided to access a raised floor area or a mezzanine, or to access areas on a story that are at different elevations due to a sloping site.
Picture
Open stair connecting two levels within a lobby. (Image courtesy of Ceslou, CC BY-SA 4.0)

​If the open stair is not used as part of the means of egress, the IBC would view it as simply a "stairway." If it is on the path of egress, it then becomes an exit access stairway. In either case, since this type of stair does not connect multiple stories, there is no code requirement to enclose the stairway or provide a rated separation (IBC 1019.2).

One other important point for this type of open stair is the requirement for accessible means of egress (IBC 1009). An exit access stair connecting levels on the same story is not permitted to be part of an accessible means of egress, unless the stair is providing the means of egress from a mezzanine (IBC 1009.3.1). If you are not sure how to address required vs. accessible means of egress requirements, check out this post for more details.

Stairway Connecting Two Stories
If your open stair does connect two stories, a few additional requirements are triggered. First, IBC 712.1.9 gives a number of requirements for vertical two-story openings. These include:
  • Does not penetrate a horizontal assembly separating a fire area or smoke compartment
  • Is not concealed within a wall, floor or ceiling assembly
  • Is not open to a Group I or R corridor
  • Is not open to any corridor on a nonsprinklered floor
  • Is separated from openings serving other floors by construction conforming to required shafts
Picture
An open stair connecting two stories.

​If your open stair is part of the means of egress (exit access stairway), IBC 1019.3 gives similar requirements. Note that open stairs connecting two stories are not permitted in Group I-2 and I-3 occupancies.

Stairway Connecting Three or More Stories
If your open stair connects three or more stories, the most common approach is to use a draft curtain and closely spaced sprinklers per IBC 1019.3.4. Use of this provision requires the following:
  • The building must be fully sprinkler-protected in accordance with NFPA 13
  • The area of the vertical opening must not exceed twice the horizontal projected area of the stairway
  • The opening must be protected with a draft curtain and sprinklers per NFPA 13
Picture
An open stair connecting multiple stories with a draft curtain and closely-spaced sprinklers. (Image courtesy of HDI Railing Systems)

​In Group B and M occupancies, there is no limit to the number of stories that can be connected with this approach. In all other occupancies, this is limited to four connected stories, except Groups I-2 and I-3, where it is not permitted at all.

Open Stairs in Group R Occupancies
In Group R-1, R-2 and R-3 occupancies, open stairs up to four stories are permitted if they are contained within a single dwelling unit, sleeping unit or live/work unit.


Open stairs are also permitted in Group R-3 congregate living facilities and Group R-4 occupancies.
Picture
An open stair located in a Group R-2 dwelling unit.

​Open Stairs within an Atrium

If located within an atrium, open stairs are permitted with no limit to the number of stories connected. Keep in mind that atriums have a host of additional requirements in the code, such as smoke control and rated separation from other building spaces.  Open stairs in an atrium are permitted to serve as exit access stairways, though the travel distance when using such stairs is limited to 200 feet (IBC 404.9.3).
Picture
An open stair connecting several levels within an atrium. (Image courtesy of Nheyob, CC BY-SA 3.0)

​Other Situations
There are a few other situations where the code allows open stairs without any rated enclosure or separation:
  • In open parking garages where the stair serves only the parking garage
  • In smoke-protected or open-air assembly seating areas complying with IBC 1029.7
  • In theaters, auditoriums and sports facilities, open stairs connecting balconies, galleries or press boxes to the main assembly floor
  • Stairs within mall buildings complying with IBC 402

Conclusion

There are many cases where the IBC allows open stairs. When open stairs are used as part of the means of egress for a building, they are considered "exit access stairways." Otherwise, they would fall under the "stairway" definition in the code. If your project is required to comply with NFPA 101, be sure to check out Chapter 8, which has more stringent requirements for vertical openings than the IBC.
26 Comments

Determining Grade Plane for a Building

2/12/2021

4 Comments

 
UPDATE: See new average grade plane calculator, linked below.
In the past few months, I've had several clients ask me questions regarding grade plane calculations - most often related to determining whether a particular story counts as a story above grade plane or as a basement. Here is quick rundown of how to do the calculation and the implications.

Average Grade Plane

Chapter 2 of the IBC defines Grade Plane (often referred to synonymously as Average Grade Plane) as:

A reference plane representing the average of finished ground level adjoining the building at exterior walls.

So if you have a completely flat site, the elevation where the finished ground level adjoins the building exterior walls is your grade plane. If your site is sloped, you need to take several elevations where the finished ground level adjoins the building and average them to determine the grade plane.

The most common question I receive on this: how many elevation points do you need to account for this in average?

First, the IBC does not give any specific requirements or instructions to answer this question. Your local jurisdiction could potentially have some guidance on how they want to see the calculation performed, but in my experience, most do not.

Typically, I advise clients to base the number of elevation points on the slope of the site. If you have a relatively flat site, a small number of elevation points will give you an accurate grade plane elevation. You may only need one elevation point per face of the building. On the other hand, if you have an irregular, highly-sloped site, you will need many elevation points. I once worked on a building that was built into the side of a steep hill - there we measured the elevation every 10 feet in some areas. If in doubt, the greater number of elevation points in your calculation will result in a more accurate measurement.
Simple Grade Plane Image
A simple grade plane calculation where the site slopes uniformly.
In the simple example above, the grade plane measurement is just the average of the elevations at the end of each wall segment (e.g. for the east wall, (280+270)/2 = 275'). However, with a more severe grade, particularly where the slope is irregular, you will need to take additional measurements, as shown in the example below.
Advanced Grade Plane Image
A complicated grade plane calculation with an irregular slope.

​Another common question: What if my site slopes perpendicular to the exterior walls?
Fortunately, the definition of Grade Plane specifically addresses this:

Where the finished ground level slopes away from the exterior walls, the reference plane shall be established by the lowest points within the area between the building and the lot line or, where the lot line is more than 6 feet from the building, between the building and a point 6 feet from the building. (2015 IBC)

So you're looking for the lowest elevation point within 6 feet of the exterior wall (or less if the lot line is closer).
Picture

The Implication - Determining a Story Above Grade Plane

Why does the grade plane calculation matter? On my projects, this always comes up when a client is trying to determine whether a particular story is actually a story above grade plane or a basement.

Chapter 2 of the IBC defines "Story Above Grade Plane" as:

Any story having its finished floor surface entirely above grade plane, or in which the finished surface of the floor next above is:
  1. More than 6 feet (1829 mm) above grade plane; or
  2. More than 12 feet (3658 mm) above the finished ground level at any point.

This definition has caused some confusion in the past, so here is a step by step breakdown:
  1. Is the floor surface of the story in question located entirely above the grade plane elevation?
  2. Is the floor surface of the floor above the story in question located more than 6 feet above the grade plane elevation?
  3. Is the floor surface of the floor above the story in question located more than 12 feet above any of the grade measurements at any point along the building exterior walls?
If you answered yes to any of the three questions above, the floor in question is considered a story above grade plane.

There are numerous code requirements that differ between a story and a basement, but the most common one is complying with the allowable number of stories based on occupancy and construction type. I had a project this year where the floor surface of the level above was 5 feet, 10 inches above the grade plane elevation, just barely passing as a basement. 2+ inches more and the building would haven been one story taller, resulting in requirements for a more robust construction type, higher shaft ratings and substantial additional cost.

If your situation is that close, I suggest including a plan in the permit package that clearly shows the grade elevations around the building and shows your grade plane calculation. This makes it easy for plan reviewers to follow your logic and hopefully agree with your approach (remember, there are no specific IBC instructions or requirements for how to do the calculation).

    New Average Grade Plane Calculator

    If you need to perform a grade plane calculation or are wondering if a particular floor is considered a story above grade plane, check out this new calculator at the link below!
Go to the Calculator

What do you Think?

Have you had a project that required a detailed grade plane calculation? Have you every had a plan reviewer or code official disagree with your calculation? Let me know in the comment box!
4 Comments

New Cheatsheet for Delayed Egress Doors

2/8/2021

0 Comments

 
Delayed egress doors are one of the most commonly-used features in design situations where some level of access control is needed on the path of egress. Under normal conditions, delayed-egress doors are a deterrent to building occupants, limiting access through the door unless necessary for an emergency. During an emergency, the delay function will deactivate (whether upon loss of power, or sprinkler/fire alarm activation), effectively making the door a normal egress door.

Similar to the other cheatsheets I have put together, this one is motivated by numerous architect requests for clarification as to when a delayed egress door can be provided.

    Enter your email to download the Delayed Egress Cheatsheet!

Download Now
0 Comments
    Picture
    Interested in Sponsoring?

    Categories

    All
    Calculators
    Chapter 10 - Means Of Egress
    Chapter 11 - Accessibility
    Chapter 14 - Exterior Walls
    Chapter 1 - Scope And Administration
    Chapter 24 - Glass And Glazing
    Chapter 2 - Definitions
    Chapter 33 - Safeguards During Construction
    Chapter 4 - Special Detailed Requirements
    Chapter 5 - General Building Heights And Areas
    Chapter 6 - Types Of Construction
    Chapter 7 - Fire And Smoke Protection Features
    Chapter 9 - Fire Protection Systems
    Cheat Sheets

    RSS Feed

      Signup to Receive Building Code Blog Updates

    Submit

    Archives

    March 2023
    February 2023
    January 2023
    November 2022
    October 2022
    March 2022
    February 2022
    January 2022
    November 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019

Home

About

Blog

Contact

Copyright © 2019-2023 The Building Code Blog
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, including the author's employer and the International Code Council, nor does the presented material assume responsibility for its use.  Local codes and amendments may vary from the code requirements described herein. Fire protection and life safety systems constitute a critical component of public health, safety and welfare and you should consult with a licensed professional for proper design and code compliance.
  • Home
  • Blog
  • About
  • PE Roadmap
  • Tools
    • Allowable Height & Area Calculator - Separated Mixed Occupancy
    • Allowable Height & Area Calculator - Non-Separated Mixed Occupancy
    • Average Grade Plane Calaculator
    • Calculated Fire Resistance for Wood Walls
    • Fire and Smoke Damper Tool
    • Fire Wall/Exterior Wall Intersection Tool
    • Frontage Calculator
    • IBC Occupant Load Calculator
    • Plumbing Fixture Calculator
    • Stair Pressurization Estimator
  • Startup