The Building Code Blog
  • Home
  • Blog
  • About
  • PE Roadmap
  • Tools
    • Allowable Height & Area Calculator - Separated Mixed Occupancy
    • Allowable Height & Area Calculator - Non-Separated Mixed Occupancy
    • Average Grade Plane Calaculator
    • Calculated Fire Resistance for Wood Walls
    • Fire and Smoke Damper Tool
    • Fire Wall/Exterior Wall Intersection Tool
    • Frontage Calculator
    • IBC Occupant Load Calculator
    • Plumbing Fixture Calculator
    • Stair Pressurization Estimator
  • Startup

The Building Code Blog

IBC Occupant Load Calculator

4/23/2021

2 Comments

 
New on the blog today is an occupant load calculator based on factors from the 2015, 2018 and 2021 editions of the IBC. Check it out at the link below!
Picture

    Check Out the Occupant Load Calculator

Submit
2 Comments

New Fire Wall/Exterior Wall Intersection Tool

4/16/2021

2 Comments

 
New on the blog today is a tool that assists in determining wall rating requirements when you have a fire wall that intersects an exterior wall. IBC 706.5.1 gives two options for this condition, one of which is drawing an imaginary lot line between the two exterior walls. Check it out at the link below!
Picture

    Access the Fire Wall/Exterior Wall Tool

Submit
2 Comments

New Fire And Smoke Damper Tool

4/9/2021

0 Comments

 
After a really nice response on the fire and smoke damper cheatsheet I have created a questionnaire tool that makes the process way easier. You answer a series of yes/no questions and the tool kicks out the damper requirement and code reference! Enter your info below to checkout the tool...
Picture

    Check out the Fire and Smoke Damper Tool

Submit
0 Comments

Group I-2 Code Changes in the 2021 IBC

4/2/2021

1 Comment

 
The 2021 IBC includes several changes that impact Group I-2 occupancies. These changes build upon updates from 2018 edition and continue with the sub-grouping of occupancies into either Condition 1 or 2 that started in the 2015 edition. As a quick reminder, IBC 308.3 defines these as:

Group I-2, Condition 1: "facilities that provide nursing and medical care but do not provide emergency care, surgery, obstetrics or in-patient stabilization units for psychiatric or detoxification, including but not limited to nursing homes and foster care facilities."

Group I-2, Condition 2: "facilities that provide nursing and medical care and could provide emergency care, surgery, obstetrics or in-patient stabilization units for psychiatric or detoxification, including but not limited to hospitals."
Picture
Group I-2 code changes impact facilities such as hospitals, nursing homes and surgery centers (Image courtesy of Johns Hopkins Hospital).

Corridor Doors

The 2021 IBC provides two changes related to corridors doors in Group I-2 occupancies.

First, Section 407.3.1.1 has been added for corridor doors that are not required to have a fire protection rating. Generally, Group I-2 corridor walls are not required to have a fire-resistance rating unless they are part of an enclosure for an exit or vertical opening, or if they are separating an incidental use room that requires a rating per IBC 509.4.

This new section now addresses the following:
  • Solid doors, which are now specifically required to have close fitting operational tolerances, head and jamb stops
  • Dutch-style doors, which are now specifically allow, but must have the following features:
    • An astragal, rabbit or bevel at the meeting edge of the upper and lower sections
    • Latching hardware on both the upper and lower sections
    • Hardware that connects the upper and lower sections, allowing them to function as a single leaf
  • Makeup air: when used to provide makeup air for exhaust systems (per Section 1020.6 Exception 1), doors are now specifically permitted to have either louvers OR up a 2/3" bottom gap
Picture
Dutch doors are now explicitly permitted in Group I-2 occupancies, but require latching hardware on both sections (not provided in the image above) (Image courtesy of K-Bid.com).

​Second, Section 407.6.1 has been added for automatic-closing doors on hold-opens. Previously, these doors were only required to close upon actuation of a smoke detector or loss of power to the hold-open or smoke detector. Now, these doors must also close upon activation of the fire alarm system or sprinkler system.

Exit Access Through Care Suites

Section 407.4.4.3 has been revised and no longer considers the number of doors or care suites in the path of exit access. Previously, this code section limited exit access to not require passage through more than three doors before reaching the corridor. Now, the code does not provide a maximum number of doors and simply limits care suites to no more than 100' of travel to reach a corridor. When a care suite requires two exit access doors, the second exit access door must lead directly to a corridor, exit or adjacent care suite.

Nursing Home Cooking Facilities

The 2021 IBC makes an organizational change to requirements for nursing home cooking facilities, moving the requirements for the cooking appliances into a separate section. This builds upon a change in the 2018 edition, which provided specific provisions to allow cooking facilities to be open to the corridor in Group I-2, Condition 1 occupancies.

Under the 2021 IBC, these requirements are now organized as follows:

Nursing Home Cooking Facilities (407.2.6): In Group I-2, Condition 1 occupancies, spaces containing a cooking facility with a domestic cooking appliance are permitted to be open to the corridor when all of the following criteria are met:
  • No more than 30 care recipients in the smoke compartment containing the cooking facility (or served by the facility)
  • No more than one cooking facility per smoke compartment
  • A clearly delineated corridor space is provided
  • The cooking facility can not obstruct access to the exit
  • The cooking appliance must comply with 407.2.7

Domestic Cooking Appliances (407.2.7): In Group I-2 occupancies, cooking appliances in domestic cooking facilities must comply with the following:
  • Appliances limited to ovens, cooktops, ranges, warmers and microwaves
  • Domestic cooking hood installed in accordance with IMC 505 provided over cooktops and ranges
  • Cooktops and ranges protected with Section 904.14.1, which requires either a fire extinguishing system in the hood OR a burner that is listed to prevent ignition of cooking oils. While the code does not give a specific standard for the listing, any appliances listed to the new Section 60A in UL 858 would meet this criteria. In the US, electric burners sold after April 2019 are required to meet this criteria.
    • This requirement does not apply for cooktops and ranges used for care recipient training or nutritional counseling purposes
  • A fuel/electrical power shutoff for the cooking equipment is provided in a staff-only area
  • A timer is provided that automatically deactivates the equipment in 120 minutes or less
  • A fire extinguisher is provided within 30 feet of each domestic cooking appliance
UL 858 Burner
Electric burners listed to UL 858 typically have a temperature-sensing element that can regulate the burner temperature to prevent ignition of grease.

Conclusion

The 2021 IBC includes several changes related to Group I-2 occupancies. These changes build upon provisions enacted during past cycles and include changes to corridor doors, care suite arrangement and nursing home cooking facility requirements.
1 Comment
    Picture
    Interested in Sponsoring?

    Categories

    All
    Calculators
    Chapter 10 - Means Of Egress
    Chapter 11 - Accessibility
    Chapter 14 - Exterior Walls
    Chapter 1 - Scope And Administration
    Chapter 24 - Glass And Glazing
    Chapter 2 - Definitions
    Chapter 33 - Safeguards During Construction
    Chapter 4 - Special Detailed Requirements
    Chapter 5 - General Building Heights And Areas
    Chapter 6 - Types Of Construction
    Chapter 7 - Fire And Smoke Protection Features
    Chapter 9 - Fire Protection Systems
    Cheat Sheets

    RSS Feed

      Signup to Receive Building Code Blog Updates

    Submit

    Archives

    March 2023
    February 2023
    January 2023
    November 2022
    October 2022
    March 2022
    February 2022
    January 2022
    November 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019

Home

About

Blog

Contact

Copyright © 2019-2023 The Building Code Blog
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, including the author's employer and the International Code Council, nor does the presented material assume responsibility for its use.  Local codes and amendments may vary from the code requirements described herein. Fire protection and life safety systems constitute a critical component of public health, safety and welfare and you should consult with a licensed professional for proper design and code compliance.
  • Home
  • Blog
  • About
  • PE Roadmap
  • Tools
    • Allowable Height & Area Calculator - Separated Mixed Occupancy
    • Allowable Height & Area Calculator - Non-Separated Mixed Occupancy
    • Average Grade Plane Calaculator
    • Calculated Fire Resistance for Wood Walls
    • Fire and Smoke Damper Tool
    • Fire Wall/Exterior Wall Intersection Tool
    • Frontage Calculator
    • IBC Occupant Load Calculator
    • Plumbing Fixture Calculator
    • Stair Pressurization Estimator
  • Startup