The IBC offers 3 approaches to mixed occupancy buildings: accessory, nonseparated and separated. Any building with two or more occupancy types must choose one or more of these approaches for compliance. In this post, we will cover all three of these approaches and the specific requirements related to each.
Nonseparated Mixed Occupancy
In a nonseparated occupancy approach, there is no requirement for a fire-rated separation between adjacent occupancies. However, the key requirement in a nonseparated occupancy approach is that the most restrictive requirements for the allowable height, area and number of stories, as well as the most restrictive fire protection requirements must be applied throughout the entire building. For example if your building has two occupancy types and one of them requires a voice fire alarm system, a nonseparated occupancy approach would mean that you need to provide a voice fire alarm system throughout the building.
If your building falls within the allowable height and area for the occupancy types involved and you can meet the fire protection requirements of the most restrictive occupancy, a nonseparated mixed occupancy approach is the easiest from a design standpoint because there is no additional requirements for rated separations. Check out the Nonseparated Mixed Occupancy Calculator
The general approach for code compliance in a non separated mixed occupancy building is:
1. Determine the maximum allowable height, area and number of stories for each occupancy involved and verify that your building meets the most restrictive requirements. 2. Determine the fire protection requirements from IBC Chapter 9 for each occupancy involved and apply the most restrictive requirements throughout the building. If the building is a high-rise, the requiremetns of Section 403 would also apply throughout. 3. Apply all other code requirements, such as means of egress, to each individual occupancy classification individually for that portion of the building. Note that even if you are taking a nonseparated occupancy approach there are specific requirements for buildings containing Groups H, I and R for a rated separation between those occupancies and adjacent building spaces you can review those requirements in IBC Chapter 4. Separated Mixed Occupancy
The separated mixed occupancy approach is typically provided when the non-separated approach is not an option. With a separated mixed occupancy approach, a fire-rated separation is typically provided between each occupancy type. IBC Table 508.4 is referenced for the specific rating requirement, though a rated separation may not be required between occupancies of a similar hazard level.
The allowable height and number of stories is applied for each individual occupancy type. For example, if your construction type limits a Group A occupancy to 4 stories, your building could be taller as long as the Group A occupancy is not located above the fourth story. The allowable area is based on the sum of the ratios of the actual floor area for each occupancy divided by the allowable floor area of that occupancy. The sum of these ratios cannot exceed one for any given story. Requirements for egress and fire protection systems are applied invidivualy to each separated occupancy in the building. Check out the Separated Mixed Occupancy Calculator
The general approach for code compliance in a separated mixed occupancy building is:
Accessory Occupancy
The final option is an accessory occupancy approach. This method is applicable where there is a small portion of a building or space that is subsidiary to the main occupancy. When that smaller space is 10% or less of the total area of a story, an accessory occupancy approach can be used.
There is no required separation between the accessory and main occupancy, and the building height, area and number of stories are based on the main occupancy, not the accessory occupancy. If the building contains a Group H, I or R occupancy, those separation requirements found in Chapter 4 would still apply. Within the accessory occupancy, other code requirements such as egress and fire protection systems are based on the accessory occupancy classification, not the main occupancy. This is crucial point that confuses many people. Essentially, the accessory occupancy designation allows you to ignore the height, area and number of stories requirements for the accessory occupancy, but all of the other code requirements for the accessory occupancy still apply. For example, a large conference room located within an office building could be considered an accessory occupancy, so the limitations for height, area and number of stories for Group A-3 occupancies would not apply. But all of the other code requirements for Group A-3, including means of egress and fire protection requirements would still apply! Bonus: Fire Walls
One final option - if you are able to separate multiple occupancies using a fire wall, you create two separate buildings from a code application standpoint and you can consider each building indvidually. A fire wall is the most robust separation option available though, so its likely to be the most disruptive from a design standpoint.
Conclusion
In summary, there are three approaches to mixed occupancy buildings: non separated, separated and accessory. All buildings with multiple occupancies must use one or more of these approaches. If your building contains three mor more occupancy types, it's possible to use a combination of the approaches, such as designating an accessory occupancy and then taking a nonseparated approach for the remaining occupancies.
Need assistance on your specific project? Add Campbell Code Consulting to your team. They are a full-service code consulting and fire protection engineering firm that can help you navigate complex code challenges.
11 Comments
7/13/2022 09:51:59 pm
The requirements for accessory occupancy stipulate that the space must be auxiliary or incidental to the primary occupancy and cannot take up more than 10% of the area of the storey in which it is located. The 2012 IBC Table 503: Allowable Heights and Building Areas prohibits ancillary occupancy from exceeding the tabular values without adding increases for sprinkler protection. According to Chapter 3: Use and Occupancy Categorization, the space is assigned a unique classification. The primary occupancy and ancillary occupancy need not be separated for the majority of occupancy types. The separation allowance is not applicable to high-hazard occupancy classification Groups H-2, H-3, H-4, and H-5, although they are still required to adhere to the separation rules for separated occupancies.
Reply
9/10/2023 11:49:12 pm
Keep posting such stuff. Thanks a lot for the information.
Reply
Jesse Murphy
10/10/2024 10:16:43 pm
Code analysis for mixed use Residencial and Business
Reply
10/21/2024 09:32:01 am
Thank you for explaining the nonseparated occupancy approach so clearly! It's great to understand how the most restrictive fire protection requirements apply. If you happen to need roofing services, feel free to check out our site!
Reply
10/21/2024 09:32:59 am
I appreciate the breakdown of nonseparated occupancy requirements! It's important to know how fire protection standards affect an entire building. If you're ever in need of roofing services, visit our website anytime!
Reply
10/23/2024 08:51:42 am
Thank you for sharing this valuable insight on nonseparated mixed occupancy design! If you happen to need roofing services, feel free to visit our site.
Reply
10/23/2024 08:52:26 am
I appreciate this information on meeting fire protection requirements for mixed occupancy! If you're in need of roofing services, don't hesitate to check out our website.
Reply
11/25/2024 08:18:03 am
Thank you for this breakdown of mixed occupancy approaches! It's insightful for managing building designs effectively. If you happen to need roofing repair services, feel free to visit our site.
Reply
11/25/2024 08:19:18 am
Great explanation of mixed occupancy strategies! Understanding these options makes compliance so much easier. If roofing repairs are on your to-do list, check out our website anytime.
Reply
11/26/2024 09:15:53 am
Thank you for the insight on nonseparated occupancy! It's great to know how the most restrictive requirements need to be applied throughout the building. If you happen to need a roofing repair, feel free to visit our site!
Reply
Leave a Reply. |
Categories
All
Sign up to receive Building Code Blog Updates |