As I have spent time in existing buildings over the years, whether surveying a building for potential renovations, reviewing existing conditions or doing inspections, the concept of the building “meeting code” often comes up. Building owners, building maintenance staff, or anyone that is concerned with the operation or maintenance of a building wants to know if their building is up to code. Or in some cases, where money for repairs or improvements is hard to come by, they don’t want to know. Unfortunately, “meeting code” can mean several different things, and it is easy to lose track of which codes actually apply to an existing building. In this post, we’ll explore the various building and fire codes that could apply to your existing building. There are many other codes (e.g. electrical, elevator) that we won’t specifically address, but the general thought process for those is similar. All references will be to the 2021 ICC codes, but many states and local jurisdictions modify these requirements, so be sure to verify the specific requirements for your area. Note: If your building is a one or two family dwelling or a townhouse, the International Residential Code (IRC) is likely the applicable code. The IBC and IEBC typically do not apply to such buildings. Existing Building Scenario 1: Normal OperationsIf you have an existing, permitted, occupied building that is proceeding with normal operations (meaning there is no construction activity occurring and you are not changing the use or occupancy of the building from the original design), “meeting code” is fairly simple. IBC/IEBC ComplianceFirst, the International Building Code (IBC) and International Existing Building Code (IEBC) generally do not apply to your building. The application of both codes is limited to situations where some level of work is occurring to the building. For example, IBC 102.3.2 states: The legal occupancy of any building existing on the date of adoption of this code shall be permitted to continue without change, except as otherwise specifically provided in this code, the International Fire Code or International Property Maintenance Code, or as is deemed necessary by the building official for the general safety and welfare of the occupants and the public. In other words, the IBC does not require any change to your building unless there is a specific requirement in the International Fire Code (IFC), International Property Maintenance Code (IPMC), or the code official determines there is a required change necessary because of a threat to public safety. We’ll get to the IFC and IPMC shortly, but the final point is an important one to note. The code language does give the Building Code Official the authority to require a change to your building if they deem it is necessary for safety reasons. In my experience, this authority is typically reserved for use when there is a clear danger to occupant safety. As a hypothetical example: if your building has an exit stairway that does not have any handrails, even though it was permitted that way from the beginning, the code official could deem the lack of handrails a big enough safety risk that they require you to install them. Assuming your building does not have any blatant safety risks, though, it’s unlikely that the code official would use this language to force a change in your building. Similar to IBC Section 102.3.2, the IEBC has the exact same language in Section 101.4. Additionally, the overall scoping language in IEBC 101.2 states that the provisions of the IEBC apply to the “repair, alteration, change of occupancy, addition to and relocation of existing buildings.” So if you are not performing any of those actions on your building, the IEBC does not apply. What about NFPA 101?If you are in a jurisdiction that adopts NFPA 101, there are additional requirements you need to consider. Unlike the ICC, which separates the IBC and IEBC into two different codes, NFPA 101 applies to both new and existing buildings. For example, NFPA 101 Section 7.1.1 states “Means of egress for both new and existing buildings shall comply with this chapter.” NFPA 101 Chapters 7-11 all apply to both new and existing buildings, so you’ll need to review these chapters for specific existing building requirements that could apply to your situation. After Chapter 11, NFPA 101 contains occupancy-specific chapters that only apply if those occupancies are in your building. These chapters alternate between new and existing occupancies (for example, Chapter 12 applies to new assembly occupancies and Chapter 13 applies to existing assembly occupancies). So the requirements found in any of the applicable “existing” chapters in NFPA 101 would also apply to your building. IFC ComplianceSecond, certain portions of the IFC will apply to your building. The application of the IFC is divided into two categories:
IFC Construction and Design RequirementsPer IFC Section 102.1, the construction and design provisions of the IFC “apply to:
In our Scenario 1 case, Items 1 and 2 would not apply since we are an existing, permitted building. Items 3 and 4 would apply, though. Item 3 sends us to IFC Chapter 11, and, Item 4, similar to the IBC, gives the code official authority to enforce the IFC on existing buildings if they deem there to be a distinct hazard to life or property. IFC Chapter 11 primarily focuses on fire safety and means of egress requirements. A few examples include:
These requirements are fairly basic and typically are not difficult to achieve, but this would be a good section to thumb through to determine if they apply to your building. IFC Section 1103.1 details which sections of Chapter 11 apply based on the use and occupancy classifications in your building. IFC Administrative, Operational and Maintenance ProvisionsPer IFC Section 102.2, the administrative, operational and maintenance provisions of the IFC “apply to:
In our Scenario 1 case, both of these items apply. This means you’ll need to review the IFC chapters that are relevant to the given system or component of your building under consideration to determine if there are any applicable requirements. For example, if you are working with a dry-cleaning facility, there are requirements in IFC Chapter 21 that would apply to how you operate the facility and equipment. What about NFPA 1?If you are in a jurisdiction that adopts NFPA 1 in lieu of the IFC, you’ll have a little more work to determine what applies to your building. Similar to NFPA 101, NFPA 1 applies to both new and existing buildings and contains requirements for existing buildings throughout the code. You’ll need to review the chapters that are relevant to the given system or component of your building under consideration and then find the requirements for existing buildings located within those relevant chapters. Existing Building Scenario 2: Changing an Existing BuildingIf you are performing work on your building, there are additional code requirements beyond those described for Scenario 1. IEBC ComplianceThe IEBC is your first stop for determining the applicable code requirements. IEBC Section 101.2 states that the provisions of the IEBC apply to the “repair, alteration, change of occupancy, addition to and relocation of existing buildings.” So you first want to review the definitions of each of these terms in IEBC Chapter 2 and determine which apply to the work you are performing in your building. For repair work, the requirements of IEBC Chapter 4 apply. The general intent of this chapter is to maintain the existing level of code compliance in the building (at a minimum), though there are some specific additional requirements depending on the system or component undergoing repair. For relocated building, the requirements of IEBC Chapter 14 apply. For the other IEBC work classifications: alterations, changes of occupancy and additions, there are three potential compliance paths:
Prescriptive Compliance MethodThe prescriptive compliance method essentially requires the work being performed to comply with the requirements of the IBC, with a few exceptions involving situations where IBC compliance is unfeasible for an existing building. For many existing buildings, the requirements of the current edition of the IBC have progressed substantially since the building code that was in effect at the time of original construction, making any attempt to comply with the current IBC requirements difficult. Work Area Compliance MethodThe work area compliance method is the most-commonly used compliance method in the IEBC and generally the most flexible from a technical requirement standpoint. This method applies varying requirements to the work area in the building based on the classification of work that is being performed. When the work area compliance method is used, the scope of work must comply with one or more of the applicable chapters:
For any building alteration, the requirements of Chapter 7 would apply. If the alteration includes “the addition or elimination of any door or window, the reconfiguration or extension of any system, or the installation of any additional equipment,” (IEBC Section 603.1), the requirements of Chapter 8 would also apply for a Level 2 alteration. If the work area exceeds 50% of the building, the requirements of Chapter 9 would also apply for Level 3 alteration. Changes of occupancy and additions using the work area compliance method must comply with Chapters 10 and 11, respectively. Finally, if you have a historic building, be sure to reference IEBC Chapter 12 first, as it modifies several the requirements found in Chapters 7-11. Performance Compliance MethodThe performance compliance method involves the evaluation of a variety of building systems and components (including height/area, compartmentation, vertical openings, means of egress, and fire protection systems). These systems are each assigned a score based on the evaluation criteria found in IEBC Chapter 13. These scores are then added to determine a total building score. If the score is high enough for the occupancy classifications involved, the work is deemed to be in compliance with the IEBC. The performance compliance method is a good option when one aspect of a proposed scope of work cannot conform to the other compliance methods, but the remainder of the building is generally compliant. For example, if an existing building work areas has excessive dead corridor lengths, compliance with the prescriptive compliance method or work area compliance method may be impossible. But the performance compliance method may be a viable option, assuming the building scores well in the other assessment areas. IBC ComplianceAs described above in Scenario 1, compliance with the requirements of the IBC is only required when specifically referenced by the IEBC (or potentially in the IFC and IPMC). That said, if your work complies with the requirements of the current edition of the IBC adopted in your jurisdiction, this will inherently satisfy the requirements of the IEBC prescriptive compliance method. What about NFPA 101?NFPA 101 Chapter 43 applies to any building rehabilitation work, including repairs, renovations, modifications, reconstruction, changes of use/occupancy and additions. Any of these actions would trigger a requirement to comply with NFPA 101 Chapter 43, which then brings in requirements to comply with other portions of NFPA 101, depending on the scope of work. Generally, NFPA 101 Chapter 43 requires compliance with all requirements found in the applicable existing occupancy chapter (Chapters 13,15,17,19, etc.) plus some additional requirements that vary based on the type of work being performed. IFC ComplianceAs described in Scenario 1, application of the IFC is divided into two categories:
IFC Construction and Design RequirementsPer IFC Section 102.1, the construction and design provisions of the IFC “apply to:
Just as in Scenario 1, Items 3 and 4 would also apply to Scenario 2. Additionally, Item 1 would also apply to the work being performed in the building (since it is creating a new condition). Therefore, any requirement found in the IFC that is applicable to a system or component within the work being performed is applicable. This means you’ll need to review the IFC chapters that are relevant to the given system or component of your building under consideration to determine if there are any applicable requirements. IFC Administrative, Operational and Maintenance ProvisionsPer IFC Section 102.2, the administrative, operational and maintenance provisions of the IFC “apply to:
What about NFPA 1There are requirements throughout NFPA 1 that would apply to Scenario 2, so again you’ll need review the chapters that are relevant to the given system or component of your building that will be changed and find the requirements for existing buildings within those chapters. ConclusionThe phrase “meeting code” is used frequently in the A/E/C world but depending on the nature of your building and the work being performed, it can mean many different things!
For an existing building, you likely fall under one of these two scenarios:
Scenario 1 typically requires compliance only with certain portions of the IFC. Scenario 2 requires compliance with the IEBC and the IFC. If you are in a jurisdiction enforcing NFPA 1 and 101, there are also requirements from these codes that apply to both scenarios.
2 Comments
The IBC offers 3 approaches to mixed occupancy buildings: accessory, nonseparated and separated. Any building with two or more occupancy types must choose one or more of these approaches for compliance. In this post, we will cover all three of these approaches and the specific requirements related to each. Nonseparated Mixed OccupancyIn a nonseparated occupancy approach, there is no requirement for a fire-rated separation between adjacent occupancies. However, the key requirement in a nonseparated occupancy approach is that the most restrictive requirements for the allowable height, area and number of stories, as well as the most restrictive fire protection requirements must be applied throughout the entire building. For example if your building has two occupancy types and one of them requires a voice fire alarm system, a nonseparated occupancy approach would mean that you need to provide a voice fire alarm system throughout the building. If your building falls within the allowable height and area for the occupancy types involved and you can meet the fire protection requirements of the most restrictive occupancy, a nonseparated mixed occupancy approach is the easiest from a design standpoint because there is no additional requirements for rated separations. The general approach for code compliance in a non separated mixed occupancy building is: 1. Determine the maximum allowable height, area and number of stories for each occupancy involved and verify that your building meets the most restrictive requirements. 2. Determine the fire protection requirements from IBC Chapter 9 for each occupancy involved and apply the most restrictive requirements throughout the building. If the building is a high-rise, the requiremetns of Section 403 would also apply throughout. 3. Apply all other code requirements, such as means of egress, to each individual occupancy classification individually for that portion of the building. Note that even if you are taking a nonseparated occupancy approach there are specific requirements for buildings containing Groups H, I and R for a rated separation between those occupancies and adjacent building spaces you can review those requirements in IBC Chapter 4. Separated Mixed OccupancyThe separated mixed occupancy approach is typically provided when the non-separated approach is not an option. With a separated mixed occupancy approach, a fire-rated separation is typically provided between each occupancy type. IBC Table 508.4 is referenced for the specific rating requirement, though a rated separation may not be required between occupancies of a similar hazard level. The allowable height and number of stories is applied for each individual occupancy type. For example, if your construction type limits a Group A occupancy to 4 stories, your building could be taller as long as the Group A occupancy is not located above the fourth story. The allowable area is based on the sum of the ratios of the actual floor area for each occupancy divided by the allowable floor area of that occupancy. The sum of these ratios cannot exceed one for any given story. Requirements for egress and fire protection systems are applied invidivualy to each separated occupancy in the building. The general approach for code compliance in a separated mixed occupancy building is:
Accessory OccupancyThe final option is an accessory occupancy approach. This method is applicable where there is a small portion of a building or space that is subsidiary to the main occupancy. When that smaller space is 10% or less of the total area of a story, an accessory occupancy approach can be used. There is no required separation between the accessory and main occupancy, and the building height, area and number of stories are based on the main occupancy, not the accessory occupancy. If the building contains a Group H, I or R occupancy, those separation requirements found in Chapter 4 would still apply. Within the accessory occupancy, other code requirements such as egress and fire protection systems are based on the accessory occupancy classification, not the main occupancy. This is crucial point that confuses many people. Essentially, the accessory occupancy designation allows you to ignore the height, area and number of stories requirements for the accessory occupancy, but all of the other code requirements for the accessory occupancy still apply. For example, a large conference room located within an office building could be considered an accessory occupancy, so the limitations for height, area and number of stories for Group A-3 occupancies would not apply. But all of the other code requirements for Group A-3, including means of egress and fire protection requirements would still apply! Bonus: Fire WallsOne final option - if you are able to separate multiple occupancies using a fire wall, you create two separate buildings from a code application standpoint and you can consider each building indvidually. A fire wall is the most robust separation option available though, so its likely to be the most disruptive from a design standpoint. ConclusionIn summary, there are three approaches to mixed occupancy buildings: non separated, separated and accessory. All buildings with multiple occupancies must use one or more of these approaches. If your building contains three mor more occupancy types, it's possible to use a combination of the approaches, such as designating an accessory occupancy and then taking a nonseparated approach for the remaining occupancies.
If you have designed a building of Type II, III, IV or V construction, you probably considered the allowable building area, which depends on the construction type, occupancy classifications, presence of fire sprinkler systems, and a few other criteria.
One common way to increase the allowable area for a building is to use a frontage increase. The frontage increase provision in the IBC, found in Section 506.3, recognizes the safety benefits of having open space directly adjacent to a building. When a fire department or other emergency responders arrive to a site, there is an increased level of effectiveness when those personnel can access a large portion of the building exterior. Using Frontage to Increase Allowable Building Area
There is no requirement for a building to use the frontage increase provisions of IBC Section 506.3, but when used, the following requirements apply:
Performing the Frontage Calculation
The frontage calculation can be performed by hand, but I recommend the building frontage calculator. If you want to do the calculation on your own, here are the steps:
1. Determine the weighted average of the width of open space (W). This value, W, is determined by the following equation:
W = (L1 x W1 + L2 x W2...)/F
Where: Ln and Wn are the length of wall segment and width of open space adjacent to that wall segment. Remember that W has to be at least 20 feet. If the width of the public way or open space is greater than 30 feet, you are required to use a maximum value of 30 feet for the calculation. F is total building perimeter fronting a public way or open space with a width of 20 feet or more.
2. Determine the total building perimeter, P.
3. Solve IBC Equation 5-5 to determine the frontage increase factor.
If = [F/P - 0.25] W/30
The frontage increase factor can then be used with IBC Equations 5-2 or 5-3 to determine the allowable area the building. You can input the If value directly into the allowable area calculator as well. Notice that with Equation 5-5, the maximum possible frontage increase factor is 0.75. In order to achieve this maximum value, the entire building perimeter has to front an open space or public way with width of 30 feet or more. If the width at any point is less than 30 feet, or if a portion of the building perimeter does not have any frontage, the frontage increase factor will be reduced. Conclusion
Using the frontage increase provisions of IBC 506.3 is a common way to increase the allowable area of a building. There is no requirement to use these provisions, but when you do, the requirement described above do apply.
When working with architects, I frequently see code summary sheets with a frontage calculation for Type I buildings that have an unlimited allowable area. Since there is no requirement to take a frontage increase, I typically remind architects they don’t need to perform the frontage calculations if the building already has an unlimited allowable area. This saves time and also prevents possible permit review comments on a code provision that wasn’t needed in the first place. NFPA 285 is the “Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Wall Assemblies Containing Combustible Components.” How’s that for a title? Despite the lengthy name, the goal of the test is quite simple – to understand how fire will spread on an exterior wall. In this article, we’ll briefly review the history of NFPA 285, discuss the criteria for the rest, and then review when compliance with NFPA 285 is required in the IBC. NFPA 285 HistoryThe NFPA 285 standard was first published in 1998 and is currently on it’s 4th edition, published in 2019. But the origins of NFPA 285 go all the way back to the 1970s, when foam plastic insulation became a popular choice for energy conservation in (or on) exterior walls. Based on work by the Society of Plastics Industry, the first test for flammability characteristics of an exterior wall was developed. This test was named UBC 17-6 and was first adopted by the Uniform Building Code (UBC) in 1988. This same test was later renamed as UBC 26-4 [1]. UBC 17-6/UBC 26-4 was a massive, full-scale test, consisting of a two-story exterior wall, totaling 24 feet in height (12 feet for each story). The test evaluated both vertical and lateral flame spread on nonload-bearing exterior walls containing foam plastics. Several wall assemblies containing foam plastics passed the test and, starting with the 1988 UBC, could be used as exterior wall assemblies in Type I, II, III and IV construction. A few years later, a modified test, using a smaller scale was adopted as UBC 26-9. 10 years after the first adoption UBC 26-4, NFPA released the first edition of NFPA 285, entitled “Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Components.” This version of NFPA 285, published in 1998, is the same as the UBC 26-9 test. Notice the difference in the name between the 1998 version of NFPA 285 and the 2019 version. The “nonload-bearing” restriction has been removed, now allowing load-bearing walls to be tested (although the standard itself does not require the application of a live load during testing). NFPA 285 Test CriteriaThe NFPA 285 testing criteria is nuanced, with variations based on the materials used in the wall assembly and the thickness of certain components in the wall assembly. For a full explanation of the acceptance criteria, review Section 10.2 of the 2019 edition of NFPA 285. Generally, the acceptance criteria involves the following: Flame propagation on the exterior face of the wall assembly
Flame propagation through combustible components and insulation Depending on the materials used in the exterior wall assembly, there are various temperature requirements that must be met. These include:
These temperature requirements apply both vertically and laterally and are measured by thermocouples placed above and to the side of the first story window opening. Temperatures in the second story
Flame Propagation to second story
Flame propagation to adjacent horizontal spaces
When is NFPA 285 Compliance Required?In the 2021 IBC, there are a number of triggers for NFPA 285 compliance. If you are using an earlier version of the code, the requirements are fairly similar, but refer to the corresponding sections in the applicable code edition for the specific details. Water Resistive Barriers (IBC 1402.5) Exterior walls in buildings of Type I, II, III or IV construction that are greater than 40 feet above grade plane must comply with NFPA 285 if they contain a water-resistive barrier. There are two key exceptions:
For this section, fenestration products, flashing of fenestration and water-resistive-barrier flashing are not considered to be part of the weather-resistive-barrier. If any of these materials are combustible, the exceptions above do not apply. Metal Composite Materials (MCMs) (IBC 1406.10.3) Exterior walls containing MCMs in buildings of Type I, II, III or IV construction that are greater than 40 feet above grade plane must comply with NFPA 285. Note that the 2021 IBC has removed several exceptions that existed in previous editions regarding the height of the MCM panels and the area of wall covered by the panels. High-Pressure Laminates (HPLs) (IBC 1408.10.4) Exterior walls containing HPLs in buildings of Type I, II, III or IV construction must comply with NFPA 285. There are two key exception for when HPLs are installed 40 feet or less above grade plane:
Mechanical Equipment Screens (IBC 1511.6.2) Compliance with NFPA 285 is one of three possible code paths for providing combustible mechanical equipment screens on the roof decks of buildings of Type I, II, III or IV construction. Foam Plastic Insulation (IBC 2603.5.5) Exterior walls containing foam plastic insulation in buildings of Type I, II, III or IV construction of any height must comply with NFPA 285. There are several exceptions:
Fireblocking (IBC 718.2.6, Exception 3) Fireblocking is not required in exterior walls when the exterior wall covering complies with NFPA 285. Key Items to KnowWall Assembly vs. Wall Components NFPA 285 tests wall assemblies as a whole. Individual components of the wall are not considered, rather the entire exterior wall assembly is evaluated for compliance with the standard. Deviation from NFPA 285 Assemblies The use of Engineering Judgements (Ejs) for NFPA 285 compliance is a well-debated topic in the design industry. On one hand, it can be impractical to test an exterior wall assembly with every possible variation of material and component (remember that NFPA 285 is a full-scale test of a specific wall assembly). But on the other hand, it can be difficult to judge how variation from a tested assembly will impact performance. While there are many exterior wall assemblies that have passed the NFPA 285 test, in my experience, many designers choose an assembly that has not been specifically tested. Many manufacturers of exterior wall products will obtain a testing report from ICC Engineering Services (an ICC ES Report, or something similar from another testing agency) that claims the product would pass NFPA 285 if tested. These reports, which essentially amount to a generalized EJ, are typically based on substituting one or more products into a wall assembly that has passed NFPA 285. If the EJ route is chosen, the EJ should be provided by a qualified design professional, such as a licensed fire protection engineer with experience in the evaluation of exterior wall assemblies. NFPA 285 vs. ASTM E119 NFPA 285 is different from ASTM E119, the test most commonly used to establish fire-resistance ratings for wall assemblies. This means that if your exterior wall is required to have a fire resistance rating, it also needs to have been tested per ASTM E119. Unfortunately, there are many walls that have a fire-resistance rating per ASTM E119 but do not pass NFPA 285. Similarly, there are walls that comply with NFPA 285 but may not be tested to ASTM E119. This means that if your exterior wall is required to have a fire resistance rating and comply with NFPA 285, there are at least four potential code paths available:
Note that the acceptance of the last two items will vary by jurisdiction. In my experience, most AHJs are satisfied by an ICC ESR report, but the acceptance of EJs can vary greatly. See the section below for more on Ejs. Finding NFPA 285 Wall Assemblies To my knowledge, the best place to find wall assemblies that have been tested to NFPA 285 is the UL database. You can search “FWFO” in the UL directory to find the list, or checkout the database below of all UL-listed assemblies. As mentioned earlier, many designers use the Engineering Judgement route to demonstrate NFPA 285 compliance. Wall assemblies using this code path are not listed in the above UL database.
Changes to the 2019 Edition The 2019 edition has been updated with a new title, now allowing for load-bearing walls, but has also been updated with a few key technical changes. A few notable changes:
It’s crucial to note that the 2019 testing requirements are in many ways more rigorous than past editions. Wall assemblies that have passed earlier editions of NFPA 285 may not comply with the 2019 edition.
In almost every building, owners or tenants have a need for some level of security or access control. The IBC covers a wide range of door locking and control techniques, but the shear number of sections and underlying requirements can be tough to digest. Many folks have trouble knowing which code sections apply, and even if the correct section is identified, it can be a challenge to understand the requirements.
In this post, I take a number of these door locking requirements and translate them into (hopefully) more clear and concise language. I also provide some general commentary on my experience in using each type of door/locking arrangement. References are provided to the last 3 editions of the IBC. Click one of the door/lock types in table below to jump to that section.
Revolving Doors
Many designers don't realize that a revolving door can be used in an egress path, as long as certain requirements are met.
All revolving doors must meet the following requirements, but be sure to check out the paragraph below this one for additional requirements for egress/non-egress doors.
|
Auto/Power Revolving Doors
|
Door Diameter (Feet)
|
Max Speed (RPM)
|
8
|
7.2
|
9
|
6.4
|
10
|
5.7
|
11
|
5.2
|
12
|
4.8
|
12.5
|
4.6
|
14
|
4.1
|
16
|
3.6
|
17
|
3.4
|
18
|
3.2
|
20
|
2.9
|
24
|
2.4
|
Revolving Doors in Egress Components must meet the following requirements:
Revolving doors that are not egress components must have a breakout force of 180 pounds or less. A breakout force of more than 180 pounds is permitted if the breakout force reduces to 130 pounds or less under one of the following conditions:
- Count towards no more than 50% or required egress width or capacity.
- Each door counts towards a maximum of 50 occupants when performing egress calculations.
- Maximum breakout force of 130 pounds.
Revolving doors that are not egress components must have a breakout force of 180 pounds or less. A breakout force of more than 180 pounds is permitted if the breakout force reduces to 130 pounds or less under one of the following conditions:
- Door power failure
- Sprinkler system activation
- Smoke detector activation with 75 feet of the revolving doors
- Activation of a manual control switch in a clearly identified location
Power-Operated Doors
Power operated doors are common in building entrances, as well as in occupancies where people may struggle to open a door by themselves, such as a Group I-2 nursing home.
Any egress door that is operated or assisted by power must have the capability to be manually opened or closed. The forces required to open the doors must comply with IBC 1010.1.3 door opening force requirements, except the force to set the door in motion must not exceed 50 pounds. The door must have the capability to open from any position to the full width of the opening when a force is applied on the egress side.
Power-operated swinging doors, power-operated sliding doors and power-operated folding doors must comply with BHMA A156.10. Power-assisted swinging doors and low-energy power-operated swinging doors must comply with BHMA A156.19. (2018 and Beyond): Low-energy power-operated sliding doors and low-energy power-operated folding doors must comply with BHMA A156.38.
Exceptions to the above requirements:
Power-operated swinging doors, power-operated sliding doors and power-operated folding doors must comply with BHMA A156.10. Power-assisted swinging doors and low-energy power-operated swinging doors must comply with BHMA A156.19. (2018 and Beyond): Low-energy power-operated sliding doors and low-energy power-operated folding doors must comply with BHMA A156.38.
Exceptions to the above requirements:
- Group I-2 occupancies
- Special purpose horizontal sliding, accordion or folding doors (see related section in this article)
- For a biparting door in the emergency breakout mode, a door leaf located within a multiple-leaf opening is exempt from the minimum 32-inch single-leaf requirement, provided that a minimum 32-inch clear opening is provided when the two biparting leaves meeting in the center are broken out.
Special Purpose Horizontal Sliding, Accordion or Folding Doors
Special purpose doors, such as horizontal sliding doors, are most commonly used in situations where a fire door is needed in an egress path but there is a desire to have the door normally open, or perhaps concealed. A sliding or folding fire shutter would fall into this category. These are the only type of doors in this article that specifically require an integrated standby power supply, typically provided as a battery pack above the door.
Horizontal sliding, accordion or folding doors can be used in all occupancies except Group H when allowed by Exception 6 of IBC 1010.1.2. Use of these doors requires the following:
- The doors are power operated and are capable of being operated manually in the event of power failure.
- The doors are openable by a simple method from both sides without special knowledge or effort.
- The force required to operate the door cannot exceed 30 pounds to set the door in motion and 15 pounds to close the door or open it to the minimum required width.
- The door must be openable with a maximum force of 15 pounds when a force of 250 pounds is applied perpendicular to the door adjacent to the operating device.
- The door assembly must comply with the applicable fire protection rating and, where rated, must be:
- Self-closing or automatic closing by smoke detection in accordance with IBC 716.2.6.6.
- Installed in accordance with NFPA 80.
- Comply with IBC 716.
- The door assembly must have an integrated standby power supply.
- The door assembly power supply must be electrically supervised.
- The door must open to the minimum required width within 10 seconds of the operating device.
Locking Arrangements in Educational Occupancies
Locking of egress doors in educational occupancies has been a hotly-debated topic in recent code cycles. Some argue that being able to lock a classroom door from the inside is necessary to protect occupants during certain emergency situations. Others argue that this actually poses a greater risk to occupants inside the classroom. The requirements for such locking arrangements are provided below.
In Group E occupancies, Group B educational occupancies and (2021 only) Group I-4 occupancies, egress doors from classrooms, offices and other occupied rooms with locking arrangements designed to keep intruders from entering the room are permitted with the following requirements:
- The door is capable of being unlocked from outside the room with a key or other approved method. Remote door unlocking is permitted in addition to the key.
- The door is openable from within the room per IBC 1010.2
- Modification are not permitted to listed panic hardware, fire door hardware or closers.
- (2021 only) Modifications to fire doors assemblies must be in accordance with NFPA 80.
Security Grilles
Secutiry grilles are an important part of building security systems, particularly in retail spaces such as a shopping mall. The IBC allows security grilles in Group M occupancies, as well as Groups B, F and S.
In Groups B, F, M and S, horizontal sliding or vertical security grilles are permitted at the main exit and must be openable from the inside without the use of a key, special knowledge or effort when the space is occupied. The grilles must remain secured in the full-open position anytime the space is occupied by the general public. Where two or more means of egress are required, no more than half of the exits or exit access doorways can be equipped with security grilles.
Group I-1 and I-2 Controlled Egress Doors
Group I-1 and I-2 occupancies include assisted living facilities, nursing homes, hospitals, psychiatric treatment centers, all facilities where people receiving care may require some level of containment. There are many situations where allowing a care recipient to freely exit may actually endanger that person or others. The IBC recognizes this risk and provides an avenue to provide locking control on egress doors in such occupancies.
Electric locking systems are permitted in Group I-1 and I-2 occupancies where the clinical needs of the care recipient require their containment. In order to use this code provision, the building must be either fully sprinkler-protected or equipped throughout with smoke detectors and meet all of the following requirements:
- The door must unlock upon actuation of the sprinkler or smoke detection system.
- The door must unlock upon power loss.
- The door must have an unlocking switch, located at the fire command center, nursing station or other approved location, that directly breaks power to the lock.
- No more than one controlled egress door before reaching an exit
- Door unlocking procures must be included and approved in the required Fire Code emergency planning (see IFC Chapter 4).
- All clinical staff must have a key or other means to operate the locked door
- Emergency lighting is required at the door.
- The door locking system must be UL 294 listed.
- Areas where persons require restraint or containment as part of the function of a psychiatric treatment area or (2021 only) cognitive treatment area.
- Where a listed egress control system is used to reduce child abduction risk from nursery and obstetric area of a Group I-2 hospital.
Delayed Egress
Using a delayed egress system is one of the most common approaches to achieve some level of access control on an egress door. They provide a deterrent to occupants using the door unless there is a true need (e.g. a fire emergency), but still allow for full egress use after the delay period. A key limitation of delayed egress systems is they are limited by occupancy , for example, Group A spaces cannot use delayed egress systems, regardless of the occupant load.
Where permitted:
2015:
Delayed egress locking systems are permitted in any occupancy except Groups A, E or H when the building is fully sprinkler protected per NFPA 13 or provided with smoke/heat detection throughout.
2018 and Beyond:
Delayed egress locking systems are permitted in the following situations when the building is fully sprinkler protected per NFPA 13 or provided with smoke/heat detection throughout.
The delayed egress locking system must meet all of the following requirements:
2015:
Delayed egress locking systems are permitted in any occupancy except Groups A, E or H when the building is fully sprinkler protected per NFPA 13 or provided with smoke/heat detection throughout.
2018 and Beyond:
Delayed egress locking systems are permitted in the following situations when the building is fully sprinkler protected per NFPA 13 or provided with smoke/heat detection throughout.
- Group B, F, I, M, R, S and U
- Group E classrooms with an occupant load less than 50
- In courtrooms, on other than the main exit doors, when the building is fully sprinkler protected per NFPA 13.
The delayed egress locking system must meet all of the following requirements:
- The delay electronics must allow immediate and free egress upon actuation of the sprinkler system or fire detection system.
- The delay electronics must allow immediate and free egress upon power loss.
- The delay electronics must have the capability to be deactivated from the fire command center or other approved location.
- When an effort is applied to the egress door hardware for not more than 3 seconds, an irreversible process must star that allows for the egress door to open in 15 seconds or less. The irreversible process must activate an audible signal near the door. Once the delayed egress door has been deactivated, the door can only be rearmed by manual means.
- Exception: Where approved by the AHJ, a delay of not more than 30 seconds is permitted.
- The egress path cannot pass through more than one delayed egress locking system.
- 2015 Exception: In Groups I-2 or I-3, the egress path can pass through up to two delayed egress locking systems if the combined delay is 30 seconds or less.
- 2018 Exception: In Groups I-2 or I-3, the egress path can pass through up to two delayed egress locking systems if the combined delay is 30 seconds or less. In Groups I-1 or I-4, the egress path can pass through up to two delayed egress locking systems if the combined delay is 30 seconds or less and the building is fully sprinkler protected per NFPA 13.
- 2021 Exception: In Groups I-1 Condition 2, I-2 or I-3, the egress path can pass through up to two delayed egress locking systems if the combined delay is 30 seconds or less. In Groups I-1 Condition 1 or I-4, the egress path can pass through up to two delayed egress locking systems if the combined delay is 30 seconds or less and the building is fully sprinkler protected per NFPA 13.
- A sign must be provided on the door and located above and within 12 inches of the door exit hardware:
- For doors swinging in direction of egress, the sign must read “PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS.”
- For doors swinging in against the direction of egress, the sign must read “PULL UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS.”
- The sign must comply with the visual character requirements in ICC A117.1.
- Exception: Where approved in Group I occupancies, the sign is not required where care recipients have a clinical needs requiring restraint or containment as part of the function of the treatment area.
- Emergency lighting must be provided on the egress side of the door.
- The delayed egress systems must be UL 294 listed.
Sensor Release of Electrically Locked Doors
Electrically locked doors using a sensor release are frequently used in situations where it is helpful to have an egress door unlock prior to an occupant physically reaching the door. Note that this type of door release functionality can be used in conjunction with an electromagnetic locking mechanism (Mag Lock).
Where Permitted:
2015:
Sensor release locks are permitted on any egress door in Groups A, B, E, I-1, I-2, I-4, M, R-1 or R-2 occupancy.
2018 and Beyond:
Sensor release locks are permitted on any egress door except in Group H occupancies.
Sensor release locks must be installed and operated per the following requirements:
2015:
Sensor release locks are permitted on any egress door in Groups A, B, E, I-1, I-2, I-4, M, R-1 or R-2 occupancy.
2018 and Beyond:
Sensor release locks are permitted on any egress door except in Group H occupancies.
Sensor release locks must be installed and operated per the following requirements:
- Sensor installed on egress side of door to detect an occupant approaching the door and cause the electric lock system to unlock.
- Door unlocks upon loss of power or signal to the sensor.
- Door unlocks upon loss of power to the lock or locking system.
- Doors can be unlocked from a manual device located 40” to 48” above the floor and with 5 feet of the doors. The unlocking device must be readily accessible and be clearly identified with a “PUSH TO EXIT” sign. The unlocking device must directly interrupt power to the lock independent of other electronics and keep the door unlocked for at least 30 seconds.
- Door unlocks upon activation of the building fire alarm system and remain unlocked until fire alarm system is reset.
- Door unlocks upon activation of the sprinkler system or fire detection system and remain unlocked until the fire alarm is reset.
- Door lock system must be UL 294 listed.
- (2021 Only) Emergency lighting must be provided on the egress side of the door.
Electromagnetically Locked Doors
Electromagnetically locked egress doors, commonly referred to as “Mag Locks” are permitted in Group A, B, E, I-1, I-2, M, R-1 and R-2 occupancies. Use of such locks requires a built-in switch on the door and compliance with the following:
- Hardware is affixed directly to the door leaf and has an obvious method of operation under all lighting conditions.
- Hardware can be operated with one hand.
- Operating the door hardware immediately interrupts power to the Mag Lock and unlocks the door immediately.
- Door unlocks upon lows of power to the locking system.
- Where panic or fire exit hardware is required, operation of that hardware also releases the Mag Lock.
- Lock system must be UL 294 listed.
Door Hardware Release of Electrically Locked Doors
Starting in 2018, the Mag Lock section above was expanded to any electric locking system with a door hardware release. The requirements here are essentially the same as the Mag lock requirements from 2015.
Door hardware release of electric locking systems on egress doors is permitted in all occupancies except Group H and requires compliances with the following:
- Hardware is affixed directly to the door leaf and has an obvious method of operation under all lighting conditions.
- Hardware can be operated with one hand and meets IBC unlatching requirements.
- Operating the door hardware immediately interrupts power to the lock and unlocks the door immediately.
- Door unlocks upon lows of power to the locking system.
- Where panic or fire exit hardware is required, operation of that hardware also releases the lock.
- Lock system must be UL 294 listed.
Correctional Facilities
Correctional and detention facilities are permitted to have locked egress doors when occupants are required to have controlled movements for security purposes. Such doors must have an egress control devices that unlocks the door manually and by at least one of the following means:
In the 2015 IBC, use of this provision is limited to Groups A-2, A-3, A-4, B, E, F, I-2, I-3, M and S occupancies within correctional and detention facilities. In 2018 and beyond, use of this section is permitted in any building within a correctional and detention facility.
- Activation of the building sprinkler system
- Actvaition of a manual fire alarm pull station
- A signal from a constantly attended location.
In the 2015 IBC, use of this provision is limited to Groups A-2, A-3, A-4, B, E, F, I-2, I-3, M and S occupancies within correctional and detention facilities. In 2018 and beyond, use of this section is permitted in any building within a correctional and detention facility.
Stairway Doors
Generally, interior stair doors must be openable from both sides without the use of a key or special knowledge, though the following exceptions allow you to lock the stair door:
In high rise buildings, stairway doors can be unlocked from the stairway side provided they have the capability of being unlocked (without unlatching) by a signal from the fire command center. when this provision is used, a telephone or other two-way communication system connected to a constantly attended location is required on every fifth floor in every stairway with locked doors.
- Stair discharge doors can be locked from the outside (must be unlocked in direction leaving the stair).
- Stair doors in high rise buildings complying with IBC 403.5.3 (see section below).
- (2015 Only): In stairs serving 4 stories or fewer, stair doors can be locked from the inside provide they have the capability of being simultaneously unlocked (without unlatching) by a signal from the fire command center or location inside the main entrance of the building.
- (2018 and Beyond): Stair doors can be locked from the inside provide they have the capability of being simultaneously unlocked (without unlatching) by a signal from the fire command center or location inside the main entrance of the building.
- Stair doors in Group B, F, M and S occupancies where the only interior access to a tenant space is from the exit stair can be locked from the inside of the stair (must be unlocked in direction of egress).
- Stair doors in Group R-2 dwelling units where the only interior access to the unit is from the exit stair can be locked from the inside of the stair (must be unlocked in direction of egress).
In high rise buildings, stairway doors can be unlocked from the stairway side provided they have the capability of being unlocked (without unlatching) by a signal from the fire command center. when this provision is used, a telephone or other two-way communication system connected to a constantly attended location is required on every fifth floor in every stairway with locked doors.
Panic and Fire Exit Hardware
Panice and fire exit hardware itself does not involve locking a door. Rather, panic or fire exit hardware can be used in conjunction with one of the locking arrangement described in this article.
I recently helped an architect design a wood-framed wall assembly with different membrane arrangements on each side of the wall. We used the calculated fire resistance approach from IBC 722 to achieve a one-hour rating for the wall. This project led me to create a new tool that calculates the fire resistance of the wall assembly based on the materials that you choose for each side. Check it out at the link below!
In the A/E world, there is much confusion regarding the definition of fire protection rating and fire resistance rating when designing doors, windows, transoms, sidelights and other openings in rated construction. These terms are often used interchangeably by mistake, but they represent two very different types of assemblies. A third term, "fire rating", is often used as well, making the distinction even more confusing. In this article, we'll review the differences between fire resistance ratings and fire protection ratings and show you how to determine the requirements for your specific situation. All code references are to the 2018 IBC.
Before distinguishing between fire-resistance-rated assemblies and fire-protection-rated assemblies, it's important to note that both of these are types of fire-rated assemblies. So if someone refers to a fire-rated glazing assembly, they could be potentially referring to either a fire-resistance-rated assembly or a fire-protection-rated assembly. The majority of the requirements for either type of assembly come from IBC Table 716.1(2).
Fire Resistance Rating
Fire-resistance-rated assemblies are those that have been tested to ASTM E119 or UL 263. This is the same test that is used for rated wall, floor and ceiling assemblies. Therefore, if you have a door, window, shutter or any other type of openings protective that is tested to ASTM E119 or UL 263, it is treated no differently than a rated wall or floor. There are no limitations to the area or location where you can provide such opening protectives.
Functionally, these tests measure an opening protective's ability to stop the transmission of smoke/flames AND to limit the transmission of radiant heat. In order to pass ASTM E119 or UL 263, assemblies must limit the temperature rise on the non-fire side of wall/floor to 250 degrees or less.
Any fire-rated glazing assembly, whether a fire-resistance-rated assembly or fire-protection-rated assembly, is required to be labelled per IBC 716.1.2.2. The markings for these assemblies are shown in IBC Table 716.1(1) and replicated in the table provided below. For fire-resistance-rated glazing, you are looking for markings containing either a "W" or "F". If the marking does not contain either of these letters, the assembly is not fire-resistance-rated. Fire doors are required to be labelled per the requirements of NFPA 80.
Functionally, these tests measure an opening protective's ability to stop the transmission of smoke/flames AND to limit the transmission of radiant heat. In order to pass ASTM E119 or UL 263, assemblies must limit the temperature rise on the non-fire side of wall/floor to 250 degrees or less.
Any fire-rated glazing assembly, whether a fire-resistance-rated assembly or fire-protection-rated assembly, is required to be labelled per IBC 716.1.2.2. The markings for these assemblies are shown in IBC Table 716.1(1) and replicated in the table provided below. For fire-resistance-rated glazing, you are looking for markings containing either a "W" or "F". If the marking does not contain either of these letters, the assembly is not fire-resistance-rated. Fire doors are required to be labelled per the requirements of NFPA 80.
Test |
Marking |
Definition |
ASTM E119 or UL 263 |
W |
Meets wall assembly criteria |
ASTM E119 or UL 263 |
F |
Meets floor/ceiling assembly criteria. |
NFPA 257 or UL 9 |
OH |
Meets fire window assembly critiera including host stream |
NFPA 252 or UL 10B or UL 10C |
D |
Meets fire door assembly criteria. |
NFPA 252 or UL 10B or UL 10C |
H |
Meets fire door assembly hose stream test. |
NFPA 252 or UL 10B or UL 10C |
T |
Meets 450 degree temperature rise criteria for 30 minutes. |
- |
XXX |
The time in minutes of the rating of the glazing assembly. |
Fire Protection Rating
Fire-protection-rated assemblies are those that have been tested to one of the following:
Functionally, these tests measure an opening protective's ability to stop the transmission of smoke/flames but do not test for the transmission of radiant heat. There are a number of limitations on the size and use of fire-protection-rated assemblies.
Area Limitations
Fire-protection-rated openings have area limitations as indicated in the table below. Remember that these apply only to fire-protection-rated assemblies. Fire-resistance-rated opening protectives are treated no differently from the wall itself and are not limited in area.
- NFPA 252, Standard Methods of Fire Tests of Door Assemblies
- NFPA 257, Standard on Fire Tests for Window and Glass Block Assemblies
- UL 9, Standard for Safety Fire Tests of Window Assemblies
- UL 10B, Standard for Fire Tests of Door Assemblies
- UL 10C, Standard for Positive Pressure Fire Tests of Door Assemblies
Functionally, these tests measure an opening protective's ability to stop the transmission of smoke/flames but do not test for the transmission of radiant heat. There are a number of limitations on the size and use of fire-protection-rated assemblies.
Area Limitations
Fire-protection-rated openings have area limitations as indicated in the table below. Remember that these apply only to fire-protection-rated assemblies. Fire-resistance-rated opening protectives are treated no differently from the wall itself and are not limited in area.
Type of Opening Protective |
Type of Wall |
Area Limitation |
Exceptions |
IBC Reference |
Fire Door |
Fire Wall |
156 SF per opening 25% of the length of the wall |
Not limited to 156 SF when both buildings are fully-sprinklered per NFPA 13 |
706.8 |
Fire Door |
Fire Barrier |
156 SF per opening 25% of the length of the wall |
Not limited to 156 SF when both buildings are fully-sprinklered per NFPA 13; No area limitations for fire doors serving rated stairs/ramps |
707.6 |
Fire Window |
Fire Barrier |
156 SF per opening 25% of the length of the wall |
Not limited to 25% of the wall when used in atrium separation walls |
707.6 |
Fire Window |
All |
25% of the wall area |
- |
716.3.2.1.2 |
Fire Doors
In interior fire doors that require a 1-hour rating or greater, fire-protection-rated glazing is permitted in the door vision panel up to 100 square inches. The glazing in the door vision panel is required to pass the hose stream test and bear the "D" and "H" markings. The duration (in hours) of the required rating depends on the type and rating of the wall itself - specific requirements are provided in IBC Table 716.1(2). If a vision panel greater than 100 square inches in area is desired, the vision panel must be fire-resistance-rated glazing and bear the "W" marking. Additionally, vision panels exceeding this area in exit stairways, ramps and passageways must meet the maximum temperature rise criteria of 450 degrees after 30 minutes and bear the "T" marking. There is an exception for this temperature rise criteria if the building is fully-sprinkler protected in accordance with NFPA 13 or 13R. Finally, sidelights and transoms adjacent to fire doors that require a 1 hour rating or greater are required to have a fire-resistance-rating equal to that of the wall itself; fire-protection-rated glazing is not permitted in these.
If the fire door requires a 45 minute rating or less, fire-protection-rated glazing is permitted in the door vision panel up to the maximum size tested. There is no requirement for fire-resistance-rated glazing in such doors. Sidelights and transoms adjacent to these doors are required to have a fire protection rating of either 20 or 45 minutes depending on the location. Refer to IBC Table 716.1(2) for the specific requirements.
Fire doors in rated exterior walls have slightly different requirements. If the exterior wall has a rating greater than 2 hours, the fire door is required to have at least a 90-minute rating and a fire-protection-rated vision panel is permitted up to 100 square inches in area. Any sidelights and transoms are required to have a fire-resistance-rating the same as the wall itself.
Exterior walls rated 2 hours or less are permitted to have fire-protection-rated glazing in the door vision panel, sidelight and transom. The rating requirement for these elements is the same as the door itself.
Fire Windows
Fire-protection-rated glazing is permitted in certain fire windows in interior wall assemblies, up to a maximum rating of 45 minutes. Fire windows in fire walls and fire barriers (excluding atrium separation, incidental use separations and occupancy separations) are required to have fire-resistance rated glazing. Refer to the table below, based on requirements form IBC Table 716.1(3). Note that walls allowing fire-protection-rated glazing can be provided with fire-resistance-rated glazing as indicated, but this is not required.
In interior fire doors that require a 1-hour rating or greater, fire-protection-rated glazing is permitted in the door vision panel up to 100 square inches. The glazing in the door vision panel is required to pass the hose stream test and bear the "D" and "H" markings. The duration (in hours) of the required rating depends on the type and rating of the wall itself - specific requirements are provided in IBC Table 716.1(2). If a vision panel greater than 100 square inches in area is desired, the vision panel must be fire-resistance-rated glazing and bear the "W" marking. Additionally, vision panels exceeding this area in exit stairways, ramps and passageways must meet the maximum temperature rise criteria of 450 degrees after 30 minutes and bear the "T" marking. There is an exception for this temperature rise criteria if the building is fully-sprinkler protected in accordance with NFPA 13 or 13R. Finally, sidelights and transoms adjacent to fire doors that require a 1 hour rating or greater are required to have a fire-resistance-rating equal to that of the wall itself; fire-protection-rated glazing is not permitted in these.
If the fire door requires a 45 minute rating or less, fire-protection-rated glazing is permitted in the door vision panel up to the maximum size tested. There is no requirement for fire-resistance-rated glazing in such doors. Sidelights and transoms adjacent to these doors are required to have a fire protection rating of either 20 or 45 minutes depending on the location. Refer to IBC Table 716.1(2) for the specific requirements.
Fire doors in rated exterior walls have slightly different requirements. If the exterior wall has a rating greater than 2 hours, the fire door is required to have at least a 90-minute rating and a fire-protection-rated vision panel is permitted up to 100 square inches in area. Any sidelights and transoms are required to have a fire-resistance-rating the same as the wall itself.
Exterior walls rated 2 hours or less are permitted to have fire-protection-rated glazing in the door vision panel, sidelight and transom. The rating requirement for these elements is the same as the door itself.
Fire Windows
Fire-protection-rated glazing is permitted in certain fire windows in interior wall assemblies, up to a maximum rating of 45 minutes. Fire windows in fire walls and fire barriers (excluding atrium separation, incidental use separations and occupancy separations) are required to have fire-resistance rated glazing. Refer to the table below, based on requirements form IBC Table 716.1(3). Note that walls allowing fire-protection-rated glazing can be provided with fire-resistance-rated glazing as indicated, but this is not required.
Type of Wall Assembly |
Required Wall Rating |
Minimum Fire-Protection-Rating Glazing |
Minimum Fire-Resistance-Rated Glazing |
Fire Wall |
All |
Not Permitted |
Same as wall rating |
Fire Barriers* |
All* |
Not Permitted |
Same as wall rating |
Atrium Separations, Incidental Use Separations, Mixed Occupancy Separations |
1 |
45 minutes |
1 hour |
Fire Partitions |
1 |
45 minutes |
1 hour |
Fire Partitions |
30 minutes |
20 minutes |
30 minutes |
Smoke Barriers |
1 |
45 minutes |
1 hour |
*except those noted in the next row
Fire-protection-rated glazing is permitted in all fire windows in exterior walls, as described in the table below. IBC Table 705.8 provides requirements for opening protectives in exterior walls, so be sure to refer there as well. Depending on the fire separation distance, you may be permitted to have unprotected openings in a rated exterior walls. Conversely, if the fire separation distance is less than 3 feet, you are not permitted to have any openings in the exterior wall, even if they have a fire protection rating. Fire-resistance-rated glazing is always permitted since it must meet the same test criteria as the wall itself.
Fire-protection-rated glazing is permitted in all fire windows in exterior walls, as described in the table below. IBC Table 705.8 provides requirements for opening protectives in exterior walls, so be sure to refer there as well. Depending on the fire separation distance, you may be permitted to have unprotected openings in a rated exterior walls. Conversely, if the fire separation distance is less than 3 feet, you are not permitted to have any openings in the exterior wall, even if they have a fire protection rating. Fire-resistance-rated glazing is always permitted since it must meet the same test criteria as the wall itself.
Type of Wall Assembly |
Required Wall Rating |
Minimum Fire-Protection-Rated Glazing |
Minimum Fire-Resistance-Rated Glazing |
Exterior Walls |
Greater than 1 |
1.5 hours |
Same as wall rating |
Exterior Walls |
1 hour |
45 minutes |
1 hour |
Exterior Walls |
30 minutes |
20 minutes |
30 minutes |
Summary
There are two types of fire-rated openings protectives: fire-resistance-rated and fire-protection-rated assemblies. Fire-resistance-rated assemblies have to meet the same test criteria, ASTM E119 or UL 263, as a rated wall or floor assembly. Since the test is the same, there are no size or location limits for where you can provide fire-resistance-rated protectives. Fire-protection-rated assemblies are tested to lesser criteria and are limited in size and location. Full requirements for both types of assemblies are found in IBC Table 716.1(2).
If you have been involved in the design or installation of a fire alarm system, whether as an architect, engineer, or owner, you have probably asked the question, "Is a strobe required here?" Like all engineering questions, the answer depends on a number of factors. In this post, I will walk through the code path step-by-step to help you understand where fire alarm strobes are required.
Starting Point: Is a Fire Alarm System Required?
The starting point for determining strobes requirements is the applicable building code for your jurisdiction. If you are in the United States, this is most likely based on the International Building Code (IBC). For projects located elsewhere, this could be NFPA 5000. Buildings owned or operated by the government could also be subject to other requirements, such as the GSA PBS-P100 or UFC 3-600-01. You may also be in a jurisdiction that enforces NFPA 101, which also has requirements for fire alarm systems.
Assuming the applicable code is the IBC (all references here are to the 2018 IBC), your first step is to check Section 907.2 to determine if a fire alarm system is required for your building. This section requires a fire alarm system based on occupancy type and other building criteria, such as classification as a high-rise building. In some instances, 907.2 requires a manual fire alarm system (pull stations) and in others a smoke detection system. For the purposes of this article though, the main concern is whether any type of fire alarm system is required at all. That's because, according to IBC 907.2, if a fire alarm system is required by Sections 907.2.1 through 907.2.23, occupant notification is required.
Fire alarm equipment required outside of Section 907.2 such as duct smoke detectors or elevator emergency operations would not trigger a requirement for strobes.
Assuming the applicable code is the IBC (all references here are to the 2018 IBC), your first step is to check Section 907.2 to determine if a fire alarm system is required for your building. This section requires a fire alarm system based on occupancy type and other building criteria, such as classification as a high-rise building. In some instances, 907.2 requires a manual fire alarm system (pull stations) and in others a smoke detection system. For the purposes of this article though, the main concern is whether any type of fire alarm system is required at all. That's because, according to IBC 907.2, if a fire alarm system is required by Sections 907.2.1 through 907.2.23, occupant notification is required.
Fire alarm equipment required outside of Section 907.2 such as duct smoke detectors or elevator emergency operations would not trigger a requirement for strobes.
Fire Alarm Requirements by Occupancy
Occupancy |
Trigger for Requiring Fire Alarm System |
2018 IBC Reference |
A |
Occupant load greater than 299 or greater than 100 on floors above or below exit discharge. |
907.2.1 |
B |
Occupant load greater than 499 or greater than 100 on floors above or below exit discharge. Always required for ambulatory care facilities. |
907.2.2 |
E |
Occupant load greater than 50. |
907.2.3 |
F |
Occupant load greater than 499 on floors above or below exit discharge AND 2 or more stories. |
907.2.4 |
H |
Group H-5 occupancies and in occupancies used for the manufacture of organic coatings or containing highly toxic gases, organic peroxides or oxidizers. |
907.2.5 |
I |
Required in all Group I occupancies. Occupant notification not required where private mode signaling is approved by code official. |
907.2.6 |
M |
Occupant load greater than 499 or greater than 100 on floors above or below exit discharge. |
907.2.7 |
R-1 |
Required in all Group R-1 occupancies. There is an exception for buildings 2 stories and smaller with sleeping units that have direct exterior exits. |
907.2.8 |
R-2 |
Required in R-2 occupancies that are 3 or more stories above lowest exit discharge, 2 or more stories below highest exit discharge or greater than 16 units. There are exceptions for buildings 2 stories and smaller with sleeping units that have direct exterior exits OR sprinklered occupancies with no interior corridors or open corridors. Also required in Group R-2 college and university buildings. |
907.2.9 |
Fire Alarm Requirements for Specific Situations
In addition to the occupancy requirements above, IBC 907 provides requirements for specific building situations.
Criteria |
Trigger for Requiring Fire Alarm System |
2018 IBC Reference |
Special Amusement Buildings |
Required in all special amusement buildings. |
907.2.11 |
High-Rise Buildings |
Required in all high-rise buildings. |
907.2.12 |
Atriums |
Required in atriums connection more than two stories. |
907.2.13 |
High-Piled Combustible Storage |
Required in all high-piled combustible storage areas. |
907.2.14 |
Aerosol Storage |
Required in some aerosol product rooms and warehouse containing aerosol products, refer to IFC Chapter 30. |
907.2.15 |
Lumber, Wood Structural Panel and Veneer Mills |
Required in all lumber, wood structural panel and veneer mills. |
907.2.16 |
Underground Buildings |
Required in underground buildings provided with a smoke control system AND deep underground buildings. |
907.2.17 and 907.2.18 |
Covered and Open Mall Buildings |
Required when total floor area exceeds 50,000 square feet. |
907.2.19 |
Airport Traffic Control Towers |
Required in all airport traffic control towers. |
907.2.21 |
Battery Rooms |
Required when battery systems exceed the capacity found in IFC Table 1206.2. |
907.2.22 |
Capacitor Energy Storage Systems |
Required when capacitor energy storage systems exceed 3kWh capacity. |
907.2.23 |
Step Two: Are Strobes Required?
Once you have determined that a fire alarm system is required, you'll want to flip ahead a few pages to determine which rooms require strobes. The starting point is IBC 907.5.2.3:
Public Uses Areas and Common Use Areas
Strobes are required in public and common use areas, with the exception of employee work areas, which are permitted to be provided with spare circuit capacity to account for future addition of strobes if needed for hearing-impaired employees. Public use and common use are defined terms in the IBC:
Common Use: Interior or exterior circulation paths, rooms, spaces or elements that are not for public use and are made available for the shared use of two or more people.
Public Use Areas: Interior or exterior rooms or spaces that are made available to the general public.
Examples of spaces that fall under one of these categories are: lobbies, corridors, circulation areas, meeting rooms, conference rooms, assembly areas, public or shared restrooms, retail spaces, and classroom. This is by no means an exhaustive list, so you'll need to consider each space in your building to verify if it falls under the definition of public use or common use.
Groups I-1 and R-1
Strobes are required in a certain percentage of dwelling and sleeping units in Group I-1 and R-2 occupancies. Refer to the table below, replicated from IBC Table 907.5.2.3.2.
Public Uses Areas and Common Use Areas
Strobes are required in public and common use areas, with the exception of employee work areas, which are permitted to be provided with spare circuit capacity to account for future addition of strobes if needed for hearing-impaired employees. Public use and common use are defined terms in the IBC:
Common Use: Interior or exterior circulation paths, rooms, spaces or elements that are not for public use and are made available for the shared use of two or more people.
Public Use Areas: Interior or exterior rooms or spaces that are made available to the general public.
Examples of spaces that fall under one of these categories are: lobbies, corridors, circulation areas, meeting rooms, conference rooms, assembly areas, public or shared restrooms, retail spaces, and classroom. This is by no means an exhaustive list, so you'll need to consider each space in your building to verify if it falls under the definition of public use or common use.
Groups I-1 and R-1
Strobes are required in a certain percentage of dwelling and sleeping units in Group I-1 and R-2 occupancies. Refer to the table below, replicated from IBC Table 907.5.2.3.2.
Number of Units |
Units with Visible Alarms |
6 to 25 |
2 |
26 to 50 |
4 |
51 to 75 |
7 |
76 to 100 |
9 |
101 to 150 |
12 |
151 to 200 |
14 |
201 to 300 |
17 |
301 to 400 |
20 |
401 to 500 |
22 |
501 to 1,000 |
5% of total |
1,001 and over |
50 plus 3 for each 100 over 1,000 |
Group R-2
Group R-2 occupancies requiring a fire alarm system must have the capability to support strobes appliances in the future. The intent is that the fire alarm system has the capability to be modified if a hearing impaired occupant were to move into the sleeping or dwelling unit.
Group R-2 occupancies requiring a fire alarm system must have the capability to support strobes appliances in the future. The intent is that the fire alarm system has the capability to be modified if a hearing impaired occupant were to move into the sleeping or dwelling unit.
Step 3: Requirements Outside the IBC
The final step is to review other documents that could drive strobe requirements. One common question is whether or not ADA Accessibility Guidelines (ADAAG) or NFPA 72 require strobes in certain rooms. Neither of these documents actually require a fire alarm system or strobes to be installed at all. When a fire alarm system is provided, however, ADAAG brings in requirements for where visible notification is required. Similarly, NFPA is only applicable when the IBC or other applicable codes require a fire alarm system.
Assuming you are required to provide a fire alarm system, the requirements of NFPA 72 would apply (ADAAG would also apply, assuming your building is required to comply with the Americans with Disabilities Act (ADA), which is a longer discussion for another article). In most cases, if you provide a fire alarm system and a strobe layout that complies with the IBC and NFPA 72, you will meet the requirements of ADAAG.
Assuming you are required to provide a fire alarm system, the requirements of NFPA 72 would apply (ADAAG would also apply, assuming your building is required to comply with the Americans with Disabilities Act (ADA), which is a longer discussion for another article). In most cases, if you provide a fire alarm system and a strobe layout that complies with the IBC and NFPA 72, you will meet the requirements of ADAAG.
Summary
The general process for determine strobe requirements is:
- Determine if a fire alarm system is required for your occupancy and/or specific building situation in the applicable codes.
- If a fire alarm system is required, determine if visible notification (strobes) are required. The most common drivers are:
- Public use and common use areas
- Group I-1 and R-1 sleeping/dwelling units
- Check other requirements. These could be additional local codes/standards, particularly amendments or additional requirements to NFPA 72 or ADAAG.
New on the blog today is an occupant load calculator based on factors from the 2015, 2018 and 2021 editions of the IBC. Check it out at the link below!
New on the blog today is a tool that assists in determining wall rating requirements when you have a fire wall that intersects an exterior wall. IBC 706.5.1 gives two options for this condition, one of which is drawing an imaginary lot line between the two exterior walls. Check it out at the link below!
Archives
March 2022
February 2022
January 2022
November 2021
May 2021
April 2021
March 2021
February 2021
January 2021
October 2020
September 2020
August 2020
July 2020
June 2020
May 2020
April 2020
March 2020
February 2020
January 2020
December 2019
Categories
All
Calculators
Chapter 10 - Means Of Egress
Chapter 11 - Accessibility
Chapter 14 - Exterior Walls
Chapter 1 - Scope And Administration
Chapter 24 - Glass And Glazing
Chapter 2 - Definitions
Chapter 33 - Safeguards During Construction
Chapter 4 - Special Detailed Requirements
Chapter 5 - General Building Heights And Areas
Chapter 6 - Types Of Construction
Chapter 7 - Fire And Smoke Protection Features
Chapter 9 - Fire Protection Systems
Cheat Sheets